An 80 amp circuit needs 4 AWG copper wire, or 2 AWG aluminum. In NM-B cable the answer is also 2 AWG.

4 AWG copper is rated 85 amps in the 75°C column of NEC Table 310.16, the column that applies where breakers and panel lugs are listed for 75°C terminations under NEC 110.14(C). Against an 80 amp breaker that is a five amp margin — the narrowest of any size in common use. Aluminum takes two sizes larger rather than one, because 3 AWG aluminum is rated 75 amps and falls short.

This page covers the 80 amp wire size in both materials and in cable, the ground wire, how far you can run it, and the question most people searching this actually need answered: whether 80 amps is the right size at all. For conductor sizing as a subject, see wire sizes explained.

Check the Drop on Your Own 80 Amp Run

Ampacity does not change with distance, so 4 AWG copper holds at any length in conduit. Voltage drop does change, which makes the run length the figure left to set.

What This Calculator Is Set To

80 amps, 240 volts, copper, 4 AWG, and the site's standard 75°C terminations — the conduit case. If you are running NM-B cable, change Wire Size to 2 AWG: cable is held to the 60°C column where 4 AWG is only 70 amps, so the figure this returns is for a conductor you cannot use there. Switching the mode to Find wire size returns 4 AWG and names Table 310.16 as the constraint, because at 80 amps no small-conductor cap applies.

Solve for

You know your wire size. Find out how much voltage you'll lose.

Conductor material
Circuit type

Advanced options
Calculation method
Installation type
About installation type

Steel conduit increases voltage drop on AC circuits. If you're not sure, leave this on PVC.

Conductor temperature
About conductor temperature

The insulation's temperature rating, printed on the wire. 75°C covers most installations.

About dwelling services and main feeders

The whole electrical supply to a house or apartment, sized 100–400 amps. Not a sub-panel. Lets the conductor be sized to 83% of the rating, as the NEC allows for this case only — assuming no derating for ambient temperature or conductor count, which this calculator does not check.

About parallel sets per phase

Only if you're running more than one conductor per phase. Most circuits use 1.

About power factor

How much of the current does useful work. Motors are around 0.8, resistive loads are 1.0. Leave at 0.9 if unsure.

0.1 – 1.0

Percentage drop

1.0%

Voltage drop

2.40 V

Voltage at the load

237.60 V

R used, Ω/1000 ft

0.310

X used, Ω/1000 ft

0.0480

Under 3% Fine for a branch circuit — no action needed

How this was calculated
  1. Source: NEC Chapter 9, Table 9 — AC resistance and reactance, 75 °C
  2. R at 75 °C = 0.310 Ω/1000 ft (4 AWG copper, PVC conduit or direct burial)
  3. X = 0.0480 Ω/1000 ft (PVC conduit or direct burial)
  4. Power factor 0.90: cos θ = 0.900, sin θ = 0.436
  5. Z = R·cos θ + X·sin θ = 0.310 × 0.900 + 0.0480 × 0.436 = 0.300 Ω/1000 ft
  6. Z is computed from R and X by Table 9 note 2 at the power factor above, not read from the table’s effective-Z columns, which hold only at 0.85.
  7. Vd = 2 × I × L × Z ÷ 1000 ÷ sets
  8. Vd = 2 × 80 A × 50.0 ft × 0.300 ÷ 1000 ÷ 1 = 2.40 V
  9. Drop = 2.40 V ÷ 240 V × 100 = 1.0%
  10. Voltage at the load = 240 − 2.40 = 237.60 V

What Size Wire for 80 Amps?

The wire size for 80 amps is 4 AWG copper in conduit, 2 AWG copper in cable, or 2 AWG aluminum. What size wire for an 80 amp breaker is the same question with the same answer — the breaker rating is what the conductor is sized against, so nothing changes between the two phrasings.

80 Amp Wire Size in Copper

80 amp wire size in copper is 4 AWG, rated 85 amps at the 75°C column. The five amps of headroom over an 80 amp breaker is about 6 percent, which is tight enough to matter: a warm ambient or a fourth current-carrying conductor in the same raceway applies a correction factor, and there is not much to give.

One figure is worth knowing because it reframes the circuit. 85 amps is not a standard overcurrent rating — NEC 240.6(A) runs 70, 80, 90 with nothing between — so under NEC 240.4(B) the next higher standard rating is permitted where a conductor's ampacity does not land on one. 4 AWG copper may therefore be protected at 90 amps. The reader installing 4 AWG on an 80 amp breaker is using a conductor the code would allow a larger breaker on, which is part of why the next section asks whether 80 is the right number.

80 Amp Wire Size in Aluminum

80 amp wire size in aluminum is 2 AWG, rated 90 amps at 75°C, and the step from copper is two sizes rather than one. 4 AWG aluminum is 65 amps and 3 AWG aluminum is 75 — five short of 80, which is the kind of near miss that produces a confident wrong answer. The compensation is that 2 AWG aluminum ends up with a ten amp margin, wider than copper's five.

Aluminum is a reasonable choice at this size for a feeder run, where the cost per foot tells and the terminations are lugs rather than devices. They must be listed AL/CU or marked for aluminum, with an antioxidant compound on the connection and lugs torqued to the value marked on the equipment.

Why 4 AWG and Not 6 AWG

6 AWG copper is rated 65 amps at 75°C, fifteen amps short of an 80 amp breaker, and no rounding allowance closes a gap that size — 240.4(B) permits one standard step, not two. That one step reaches 70 amps and stops there, and only in conduit. 6 AWG is the answer at 60 amps, which is why it is the usual first guess here, and the jump from 60 to 80 amps costs a full conductor size in every material.

NEC 240.4(D) plays no part in any of this, and that is worth saying because readers arrive expecting it to. The small-conductor rule enumerates 18, 16, 14, 12 and 10 AWG and stops there; it does not reach 8, 6, 4, 3 or 2 AWG. At 30 amps that provision produces the answer outright and at 40 amps it eliminates the size below, but from 8 AWG upward the ampacity figure is simply the figure.

The Voltage, in Three Sentences

An 80 amp circuit is 240 volts on a two-pole breaker, and 220 or 230 volts on an older label describes the same circuit with no change to the conductor. There is no realistic 120 volt case: a single ungrounded conductor carrying 80 amps at 120 volts would deliver under 10 kW while needing the same copper as a 19 kW circuit at 240, and no keyword in this page's search data asks for it. Direct current is a different problem rather than a smaller one — an 80 amp 12 volt circuit is an alternator or inverter feed, and 4 AWG copper carrying 80 amps over ten feet at 14 volts DC drops 3.52 percent, so sizing there is governed by voltage drop from the first foot rather than by ampacity.

80 Amp Wire Size Chart

The conductor sizes either side of the answer, with both code paths and whether each size is actually manufactured as NM-B cable:

Conductor 60°C column 75°C column 90°C column Made as NM-B? Enough for 80 A?
6 AWG copper 55 A65 A75 AYesNo — fifteen amps short
4 AWG copper 70 A85 A95 AYesYes — in conduit
3 AWG copper 85 A100 A115 ANoWould suit, but is not made as cable
2 AWG copper 95 A115 A130 AYesYes — the NM-B answer
3 AWG aluminum —75 A85 ANoNo — five amps short
2 AWG aluminum —90 A100 ANoYes — the aluminum answer

In short: 4 AWG copper carries an 80 amp circuit in conduit; 2 AWG aluminum is the aluminum answer; and in cable the answer is 2 AWG copper, because the 60°C column calls for 3 AWG and 3 AWG is not made as NM-B. 6 AWG is fifteen amps short in copper and 3 AWG aluminum is five short. For the full range of sizes and every temperature column, see the NEC ampacity table.

What This Table Assumes

Table 310.16 figures describe not more than three current-carrying conductors in a raceway, cable or earth, at an ambient of 30°C (86°F). Where those conditions do not hold the ampacity is reduced before it is compared against the breaker, using the ambient correction factors of Table 310.15(B)(1) and then the adjustment factors of Table 310.15(C)(1). With only five amps of margin on 4 AWG copper, a single correction factor is enough to put an 80 amp circuit in question — 85 amps multiplied by the 0.88 factor for a 36–40°C ambient gives 74.8, below the breaker. In conduit the usual answer is 3 AWG; in cable, 334.80 permits the 90°C rating for that arithmetic provided the result does not exceed the 60°C value, so a 2 AWG cable derates from 130 amps and is then capped at 95.

Why 80 Amps at All?

80 amperes is a standard overcurrent rating under NEC 240.6(A), so breakers and panels exist for it — but it sits between the two sizes people actually install, and most of the reasons given for choosing it do not survive examination. Anyone searching this term without a modifier is quite likely unsure whether 80 amps is the right size, so it is worth answering that before anything else.

80 Amps Often Takes the Same Wire as 100

For a service or a feeder carrying the entire load of a dwelling, an 80 amp circuit and a 100 amp circuit take the identical conductor. NEC 310.12 permits a dwelling service or whole-dwelling feeder rated 100 through 400 amperes to be sized at not less than 83 percent of its rating; an 80 amp circuit is below that range and sizes from Table 310.16 at the full 80. So the 100 amp case needs 83 amps of ampacity and the 80 amp case needs 80, and both land on the same wire.

That identity holds only against a whole-dwelling service or feeder, and a sub-panel feeder carrying part of the load is a different comparison — 310.12 covers conductors supplying the entire load of a dwelling unit, so a feeder to a garage or a sub-panel gets no allowance and sizes at the full 100 amps. Since sub-panels are what most people reading this page are installing, both comparisons matter:

What is being fed Required ampacity Copper Aluminum In NM-B
80 A circuit or sub-panel feeder 80 A4 AWG2 AWG2 AWG
100 A whole-dwelling service or feeder 83 A4 AWG2 AWG2 AWG
100 A sub-panel feeder (part of the load) 100 A3 AWG1 AWGnot possible

All three rows are reproducible in the calculator above. Open Advanced options, tick "This is a dwelling service or main feeder" and switch the mode to Find wire size: at 100 amps it returns the middle row, and at 80 amps it returns a message saying the 83 percent allowance reaches only 100 through 400 amperes. That refusal is this section's point arriving from the tool rather than from the page.

So the honest answer depends on what is being fed. Against a whole-dwelling service or feeder, choosing 80 amps over 100 saves nothing at all — same conductor, same conduit, same trench, same labour — and costs twenty amps of capacity. Against a sub-panel feeder, 100 amps costs one conductor size in each material, which on a short run is a modest difference and on a long one is not. And in cable the gap is absolute: a 100 amp sub-panel feeder needs 1 AWG in the 60°C column, which exceeds the largest NM-B made, so it cannot be run in NM-B at all while an 80 amp feeder can.

There Is No 80 Percent Rule

The most common reason given for an 80 amp sub-panel is that a breaker may be loaded only to 80 percent of its rating, making 80 amps the largest feeder a 100 amp panel can supply. The current code contains no such limit on a sub-panel feeder. What governs is NEC 408.30, which requires a panelboard to have a rating not less than the minimum feeder capacity for the load calculated under Article 220, and NEC 408.36, which requires it to be protected by an overcurrent device rated not greater than the panelboard. Neither imposes an 80 percent ceiling.

Where continuous loads are involved the code works the other way round, sizing the circuit at 125 percent of the continuous load rather than derating the breaker to 80 percent of its rating. Applying both would derate the same circuit twice. The likely origin of the convention is a paragraph in the 1999 edition that did limit continuous load on a panelboard overcurrent device to 80 percent, and which was not carried into Article 408 when the code was reorganised — worth knowing as an explanation of where the habit came from, though the present-tense answer stands on 408.30 and 408.36 regardless.

When 80 Amps Is the Right Choice

Three cases survive. A load calculation under Article 220 that lands between 60 and 100 amps is the legitimate one: the panelboard has to be rated for the calculated load and the feeder sized to it, and if that calculation says 80 then 80 is correct and cheaper than 100. Equipment with an 80 amp maximum overcurrent device on its nameplate is the second, where the breaker is specified rather than chosen. The third is a 64 amp EV charger, below.

Outside those, 80 amps is usually a number someone arrived at rather than calculated. It is also worth noting where this amperage genuinely lives: the search data for it includes three-phase and 208 volt phrasings, which are commercial distribution rather than residential wiring. 80 amperes is an ordinary rating in a commercial equipment schedule and an unusual one in a house.

EV Charging at 80 Amps

An 80 amp circuit is what a 64 amp electric vehicle charger requires, under NEC 625.41, which treats EV charging as a continuous load and sizes the circuit at 125 percent of the equipment rating — 64 × 1.25 = 80 exactly. The 64 amp output is uncommon residentially: most home units draw 32 to 48 amps and want a 40, 50 or 60 amp circuit. The equipment that does draw it is a specific class of higher-output hardwired station delivering around 15 kW, and if you are not installing one of those, this is not why you need 80 amps.

Sub-Panels and Feeders

What size wire for an 80 amp sub panel is 4 AWG copper or 2 AWG aluminum, as a four-conductor feeder: two ungrounded conductors, a neutral and an equipment grounding conductor. The neutral carries the unbalanced current of the 120 volt circuits fed from the panel, and the grounding conductor is separate from it — in the sub-panel they land on separate bars, which NEC 408.40 requires of any panelboard that is not service equipment.

How Far an 80 Amp Feeder Reaches

4 AWG copper carries 80 amps about 150 feet at 240 volts before voltage drop passes 3 percent. That is further than a 60 amp feeder on 6 AWG manages, which reaches roughly 130 feet — the larger conductor more than absorbs the larger current, so an 80 amp feeder is less distance-constrained than a 60 amp one rather than more.

One-way run Drop on 4 AWG Verdict
25 ft 0.50%Fine
50 ft 1.00%Fine
100 ft 2.00%Fine
150 ft 3.00%At the limit
200 ft 4.00%Over 3% — 2 AWG

In short: 4 AWG copper is comfortable to 100 feet carrying 80 amps at 240 volts, sits exactly on 3 percent at 150 feet, and wants 2 AWG beyond that. Going up a size buys reach — 3 AWG reaches about 183 feet and 2 AWG about 236. The 3 percent figure comes from informational notes at NEC 210.19(A) and 215.2(A) and is a recommendation rather than a requirement, though it is what equipment manufacturers assume. Upsizing for voltage drop also pulls the equipment grounding conductor up proportionally under NEC 250.122(B).

What Size Ground Wire for 80 Amps?

8 AWG copper, or 6 AWG aluminum, from NEC Table 250.122. The equipment grounding conductor is sized against the rating of the overcurrent device rather than against the circuit conductors or the ampacity table, because it carries fault current only and only until the breaker opens.

Table 250.122 lists no 80 ampere row — it steps from 60 straight to 100 — so an 80 amp device reads the 100 ampere row. Seventy, eighty and ninety amp devices therefore all take the same 8 AWG copper, and the grounding conductor ends up two sizes smaller than the 4 AWG it runs beside.

Feeding a Detached Structure

A feeder to a detached building carries three requirements a sub-panel in the same building does not: a disconnecting means at the structure under NEC 225.31, located per 225.32; a grounding electrode system at the structure under NEC 250.32(A); and an equipment grounding conductor run with the feeder under 250.32(B)(1), since the older practice of bonding the neutral at the outbuilding is now an existing-installations allowance only. Those requirements are identical at every feeder size, and the 60 amp wire size page works through each of them in full.

Cable Types for an 80 Amp Circuit

Conduit and cable give different answers at 80 amps, and the cable answer is not the one the ampacity table predicts — because the size the table calls for is not manufactured.

NM-B at 80 Amps, and the Size That Does Not Exist

NEC 334.80 holds non-metallic sheathed cable to the 60°C ampacity column whatever its conductors are individually rated. In that column, 80 amps calls for 3 AWG copper, rated 85 amps. And 3 AWG is not made as NM-B. The manufactured sizes run 14, 12, 10, 8, 6, 4 and 2 AWG, so the cable answer skips the size the code points at and lands on 2 AWG, rated 95 amps at 60°C and the largest NM-B in production.

That availability is a manufacturing fact rather than a code one, taken from the cable manufacturer's own specification and catalogue, so it is worth confirming against whatever product you are actually buying.

This is the first amperage where the conductor the 60°C column requires does not exist as a cable at all — a different and sharper situation than at 60 amps, where cable simply needed one size larger than conduit. It also puts 80 amps one step from the end of NM-B entirely: a 100 amp sub-panel feeder needs 1 AWG in the 60°C column, and nothing in NM-B reaches it. Practically, 2 AWG cable is stiff, the box fill is substantial, and the cost difference against conduit and individual conductors narrows to the point where conduit is usually the better choice at this size.

THHN in Conduit

4 AWG THHN in conduit is the smaller and generally cheaper way to run an 80 amp circuit, because individual conductors terminate at 75°C and are rated 85 amps rather than the 70 the same copper reads inside cable. A raceway also lets the circuit be repulled when the load changes, which on a feeder sized to a calculation that may be revisited is worth more than the conductor saving. If a correction factor is going to apply, this is the path with somewhere to go: 3 AWG pulls into the same conduit.

Direct Burial and UF-B

UF-B carries the same 60°C limitation as NM-B under 334.80, so a direct buried 80 amp feeder runs into the same missing 3 AWG and the same 2 AWG answer. Burial depth comes from Table 300.5. These runs are long by nature, and since a buried cable cannot be repulled when the load changes, conduit with individual conductors is the stronger choice on anything beyond a short run.

Copper vs Aluminum for 80 Amps

Aluminum at 2 AWG and copper at 4 AWG are both ordinary feeder conductors at this amperage, and the choice is mostly cost against conduit fill. Aluminum is cheaper per foot and two trade sizes larger, so check the raceway rather than assuming the copper figures carry over. Terminations must be listed AL/CU or marked for aluminum, with an antioxidant compound and the marked torque. The one asymmetry worth knowing is the margin: 2 AWG aluminum has ten amps over an 80 amp breaker and 4 AWG copper has five, so aluminum is the more forgiving choice if a correction factor is likely.

Why Other Sources Give a Different Answer

Three claims come up often enough around 80 amps to be worth addressing directly, because each is reasonable on its face and each leads to a different conductor.

The 80 Percent Claim

The claim is that a sub-panel feeder may not exceed 80 percent of the supplying panel's rating, which is where "an 80 amp sub-panel off a 100 amp service" comes from. The code route is different: NEC 408.30 sizes the panelboard to the calculated load under Article 220 and NEC 408.36 limits the overcurrent device to the panelboard's rating, with no 80 percent ceiling in either. Continuous loads are handled by sizing the circuit at 125 percent rather than by derating the breaker. The practical consequence is that an 80 amp feeder is a legitimate choice when the load calculation produces it, and not merely because the supply is 100 amps.

Six Gauge, and Which Column It Comes From

A source answering 6 AWG is reading a 65 amp conductor, which is the 60 amp answer rather than the 80 amp one. A source answering 3 AWG is reading the 60°C column correctly and has not checked whether the cable is made in that size. A source answering 2 AWG may be describing cable, or aluminum, or being deliberately conservative — all three are defensible, and which one is meant changes what you should buy. Naming the column and the wiring method is what makes any of these figures usable, which is why the chart above carries both paths as separate columns.

The 83 Percent Allowance

The third claim applies NEC 310.12's 83 percent allowance to an 80 amp circuit, which produces a smaller conductor than the code permits. The allowance reaches services and feeders rated 100 through 400 amperes and only where they carry the entire load of a dwelling unit, so it does not apply at 80 amps on either count. The 100 amp wire size page is built around that allowance and shows where it does apply.

Common Mistakes on 80 Amp Circuits

The errors that occur at 80 amps come mostly from carrying a figure over from an adjacent size, which this amperage invites because so few people install it often.

Wrong Conductor

Running 6 AWG is the first, because 6 AWG is the 60 amp answer and 80 amps feels close to 60. It is fifteen amps short. Using 3 AWG aluminum is the same error with a narrower margin — 75 amps against an 80 amp breaker, five short — and it is easy to make because 3 AWG copper does satisfy the 60°C column, so the size looks familiar from the cable discussion. Specifying 4 AWG NM-B is the third: correct in conduit, seventy amps in cable.

Wrong Reasoning

Choosing 80 amps to save conductor over 100 saves nothing when the feeder carries a whole dwelling, and one size when it feeds a sub-panel. Citing the 80 percent rule as the reason for the choice rests on a limit the current code does not contain. Applying the 83 percent allowance at 80 amps produces an undersized conductor. And looking for NEC 240.4(D) and then treating its silence as though the ampacity table were also silent gets the answer wrong in the other direction — the small-conductor rule stops at 10 AWG, and Table 310.16 does not stop anywhere.

Wrong Context

Installing an 80 amp service on a house is not permitted: NEC 230.79(C) sets 100 amperes as the minimum rating for the service disconnecting means on a one-family dwelling. For a non-dwelling structure, where 230.79(D) sets a 60 ampere floor, an 80 amp service is legitimate. The remaining two are shared with every feeder size and still worth checking: omitting the grounding electrode or the disconnect at a detached structure, and bonding the neutral to the ground bar inside the sub-panel, which works until there is a fault.

Frequently Asked Questions

The questions this page's search data carries, answered in one sentence each before any qualification. Three are editorial additions, marked in place.

What size wire for 80 amps?

4 AWG copper, or 2 AWG aluminum. 4 AWG copper is rated 85 amperes in the 75°C column of NEC Table 310.16, which leaves five amps over an 80 amp breaker. Aluminum takes two sizes larger rather than one here, because 3 AWG aluminum is rated 75 amperes and falls short. In NM-B cable the answer is 2 AWG.

What size wire for an 80 amp breaker?

4 AWG copper on 75°C terminations. NEC 240.4(D) does not reach 4 AWG, so there is no small-conductor cap to apply on top of the ampacity figure and Table 310.16's 85 amperes is the governing number. Because 85 is not a standard overcurrent rating, NEC 240.4(B) would in fact permit a 90 amp breaker on the same conductor.

What size wire for an 80 amp sub panel?

4 AWG copper or 2 AWG aluminum, as a four-conductor feeder: two ungrounded conductors, a neutral and an equipment grounding conductor. The 83 percent allowance in NEC 310.12 does not apply, because it reaches only services and feeders rated 100 through 400 amperes, so the feeder sizes from Table 310.16 at the full 80 amps.

Can I use 6 AWG wire for 80 amps?

No. 6 AWG copper is rated 65 amperes in the 75°C column, fifteen amps short of an 80 amp breaker, and the next-size-up allowance in NEC 240.4(B) cannot close a gap that large. 6 AWG is the 60 amp answer, which is why it is a common first guess here. Editorial addition — no keyword in this page's data asks this.

What size aluminum wire for 80 amps?

2 AWG aluminum, rated 90 amperes at 75°C. Aluminum is two sizes larger than copper at this amperage rather than the usual one: 4 AWG aluminum is 65 amperes and 3 AWG aluminum is 75, so both fall short of 80 and the answer skips to 2 AWG. That gives a ten amp margin, wider than copper's five.

Can I use Romex for an 80 amp circuit?

Yes, in 2 AWG. NEC 334.80 holds NM-B to the 60°C column, where 80 amps calls for 3 AWG — and NM-B is not manufactured in 3 AWG, so the cable answer skips to 2 AWG, the largest NM-B made. Editorial addition — no keyword in this page's data asks this, but the size the code requires does not exist as a cable.

What size ground wire for 80 amps?

8 AWG copper, or 6 AWG aluminum, from NEC Table 250.122. The table lists no 80 ampere row — it steps from 60 to 100 — so an 80 amp device reads the 100 ampere row. Seventy, eighty and ninety amp devices therefore all take the same 8 AWG copper equipment grounding conductor.

What size wire for an 80 amp service?

An 80 amp service is not permitted on a one-family dwelling. NEC 230.79(C) sets 100 amperes as the minimum rating for the service disconnecting means on a house, so the smallest legal new dwelling service is 100 amps. For a non-dwelling structure, where 230.79(D) sets a 60 ampere floor, an 80 amp service takes 4 AWG copper or 2 AWG aluminum.

Should I install an 80 amp or a 100 amp sub panel?

For a sub-panel carrying part of a dwelling's load, 100 amps costs one conductor size: 3 AWG copper against 4 AWG for 80 amps. The comparison changes for a feeder carrying the entire dwelling load, where NEC 310.12's 83 percent allowance makes 80 and 100 amps take the identical conductor. Editorial addition — this question is not in the keyword data.

Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions; overcurrent limits apply NEC 240.4 and 240.6(A), equipment grounding conductors are from NEC Table 250.122, and voltage drop figures are computed from NEC Chapter 9 Table 9. Cable size availability is a manufacturing fact taken from the cable maker's published specification, not from the code. Figures are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.