A 15 amp breaker needs 14 AWG copper.

Two separate rules give that answer and they agree. NEC Table 310.16 rates 14 AWG copper at 15 amperes in the 60°C column — the column NEC 110.14(C)(1)(a) makes the default for circuits rated 100 amperes or less — and NEC 240.4(D)(3) caps the overcurrent device on 14 AWG copper at 15 amperes outright, whatever the table says in its warmer columns. Because the two agree, the cap does nothing visible to the answer. Where it does bite is in the other direction: 14 AWG carries 20 amperes at 75°C and 25 at 90°C, and the cap forbids protecting it at either. This page works that through, gives the grounding conductor and the cable types, covers the 240 volt case, and shows how far 14 AWG actually reaches. For how conductor sizing works as a subject, see wire sizes explained.

Check the Drop on Your Own 15 Amp Run

What This Calculator Is Set To

A 15 amp circuit in 14 AWG copper at 120 volts, 40 feet one way, at the site's standard 75°C terminations. Set your own distance and read the percentage.

Solve for

You know your wire size. Find out how much voltage you'll lose.

Conductor material
Circuit type

Advanced options
Calculation method
Installation type
About installation type

Steel conduit increases voltage drop on AC circuits. If you're not sure, leave this on PVC.

Conductor temperature
About conductor temperature

The insulation's temperature rating, printed on the wire. 75°C covers most installations.

About dwelling services and main feeders

The whole electrical supply to a house or apartment, sized 100–400 amps. Not a sub-panel. Lets the conductor be sized to 83% of the rating, as the NEC allows for this case only — assuming no derating for ambient temperature or conductor count, which this calculator does not check.

About parallel sets per phase

Only if you're running more than one conductor per phase. Most circuits use 1.

About power factor

How much of the current does useful work. Motors are around 0.8, resistive loads are 1.0. Leave at 0.9 if unsure.

0.1 – 1.0

Percentage drop

2.8%

Voltage drop

3.38 V

Voltage at the load

116.62 V

R used, Ω/1000 ft

3.100

X used, Ω/1000 ft

0.0580

Under 3% Fine for a branch circuit — no action needed

How this was calculated
  1. Source: NEC Chapter 9, Table 9 — AC resistance and reactance, 75 °C
  2. R at 75 °C = 3.100 Ω/1000 ft (14 AWG copper, PVC conduit or direct burial)
  3. X = 0.0580 Ω/1000 ft (PVC conduit or direct burial)
  4. Power factor 0.90: cos θ = 0.900, sin θ = 0.436
  5. Z = R·cos θ + X·sin θ = 3.100 × 0.900 + 0.0580 × 0.436 = 2.815 Ω/1000 ft
  6. Z is computed from R and X by Table 9 note 2 at the power factor above, not read from the table’s effective-Z columns, which hold only at 0.85.
  7. Vd = 2 × I × L × Z ÷ 1000 ÷ sets
  8. Vd = 2 × 15 A × 40.0 ft × 2.815 ÷ 1000 ÷ 1 = 3.38 V
  9. Drop = 3.38 V ÷ 120 V × 100 = 2.8%
  10. Voltage at the load = 120 − 3.38 = 116.62 V

What Size Wire for a 15 Amp Breaker?

14 AWG copper, and a 15 ampere breaker is the largest device 14 AWG copper may ever have. That second half is the part worth keeping, because it is what makes the first half true no matter which column of the ampacity table you happen to be reading.

Why the Answer Does Not Depend on the Temperature Column

On most pages on this site the termination temperature decides the conductor, and readers who have arrived from the larger amperages will expect to have to pick a column. Here it does not matter. 14 AWG copper is 15 amperes at 60°C, 20 at 75°C and 25 at 90°C, and NEC 240.4(D)(3) holds its overcurrent device to 15 amperes in all three cases. The warmer columns describe what the conductor can carry; they do not change what may protect it.

Oversizing Is Always Permitted

Nothing requires a conductor to match its breaker. The breaker exists to protect the conductor, so a conductor larger than the minimum is protected further below its capacity and is permitted at any rating. 12 AWG copper on a 15 ampere breaker is a legitimate circuit and sometimes the better one. When it is actually worth the money rather than merely allowed:

  • On a long run. 14 AWG reaches about 40 feet at a full 15 amperes before the drop passes 3 percent. 12 AWG, with about two-thirds the resistance per foot, reaches roughly 60. On a run to a detached garage or a far bedroom this is the deciding factor, and it is a voltage-drop decision rather than an ampacity one.
  • Where the circuit may be uprated later. A 12 AWG circuit can take a 20 ampere breaker afterwards under NEC 240.4(D)(5); a 14 AWG circuit can never be uprated without replacing the conductor. If the room is likely to gain a window air conditioner, the cable is the cheap part of that decision.
  • Where correction factors apply. The 240.4(D) cap is applied after any ambient-temperature or conductor-count correction, so a cable in a hot attic or bundled with others is working from a corrected ampacity rather than the tabulated one. Starting a size larger leaves room for that.

How Far 14 AWG Actually Reaches

This is the shortest reach of any rating on this site, and it surprises people. At a full 15 amperes on a 120 volt circuit, 14 AWG copper passes the 3 percent advisory figure at roughly 40 feet one way. At the 12 amperes a general-purpose circuit is more likely to carry it reaches about 50 feet. On a two-pole 240 volt circuit the same conductor reaches about 80 feet, because the percentage is measured against twice the voltage.

Forty feet is not a long run by any ordinary standard — it is a kitchen to a far bedroom, or a panel to a detached garage. The conductor stays entirely legal past it: the NEC's voltage-drop figures live in informational notes and NEC 90.5(C) makes notes advisory rather than enforceable. What happens instead is that lights dim when a motor starts and the far end of the circuit works worse than the near end. The fix is a larger conductor, not a larger breaker — which is the one place on this page where the thin wire rather than the rule is the constraint.

The Reverse Is Not Permitted

14 AWG cannot serve a 20 amp breaker — the same NEC 240.4(D)(3) that caps the device at 15 amperes forbids it, and 20 amp wire size works that case through from a 20 amp starting point, which is where a reader who already has the breaker is standing.

The Cap Is on the Breaker, Not the Wire

Three numbers land on 15 at this rating and they come from three different places in the code. 14 AWG copper's ampacity in the 60°C column is 15 amperes. NEC 240.4(D)(3) caps its overcurrent device at 15 amperes. The standard rating actually fitted, from NEC 240.6(A), is 15 amperes. Because all three agree, nothing on this page looks like it is being limited — and that is exactly why the rule gets missed.

What the Cap Actually Does

NEC 240.4(D) limits the overcurrent device. It does not reduce the conductor's ampacity, and it does not say 14 AWG copper is a 15 ampere conductor — the table says 20 amperes at 75°C and the table is right. The two numbers answer different questions. Ampacity is what the conductor may carry continuously; the cap is the largest device permitted to protect it. Conflating them is how the 14 AWG mistake gets rationalised after the fact.

The provision also applies after correction factors, not before. Its own words are that the protection shall not exceed the listed values "after any correction factors for ambient temperature and number of conductors have been applied" — so derating a cable in a hot space reduces the conductor's usable ampacity, and the 15 ampere ceiling on the device stays where it is regardless.

There Is No Special Case Here

On several larger pages one application inverts the ordinary answer — a nameplate, a duty cycle, a cable type on one side of a disconnect. At 15 amperes there is no such application. The cap is a ceiling rather than an override: it limits the device for every use of 14 AWG copper equally, in every wiring method, for every load. Saying so is the honest answer, and a page that manufactured an exception here would be inventing one.

15 Amp Wire Size Chart

Conductors around 15 amperes: NEC Table 310.16 ampacity in all three columns, against the NEC 240.4(D) limit on the overcurrent device
Conductor 60°C — the default at 15 A 75°C 90°C Max breaker — 240.4(D)
14 AWG copper 15 A20 A25 A15 A — (D)(3)
12 AWG copper 20 A25 A30 A20 A — (D)(5)
10 AWG copper 30 A35 A40 A30 A — (D)(7)
12 AWG aluminum —20 A25 A15 A — (D)(4)
10 AWG aluminum —30 A35 A25 A — (D)(6)

Three Ampacities, One Ceiling

Read the 14 AWG copper row across. Three ampacities, one ceiling — and the ceiling is the number that decides what breaker may be fitted. The subsection is given against each row because it is the part a reader takes to the code book; the caps are not one rule but seven separate entries, and the copper and aluminum sizes interleave rather than running in order.

The aluminum rows show a dash in the 60°C column because NEC Table 310.16 publishes no 60°C aluminum column — a dash there is the absence of a published value, not a zero. There is no 14 AWG aluminum row at all: the table starts aluminum at 12 AWG, so at 15 amperes copper is the only conductor the table offers.

For every conductor size and temperature column in one place, see the NEC ampacity table.

Grounding a 15 Amp Circuit

The equipment grounding conductor for a 15 ampere circuit is 14 AWG copper, or 12 AWG aluminum, from NEC Table 250.122.

Equipment grounding conductor for a 15 amp circuit, by the circuit conductor it runs with
Circuit conductor EGC — Table 250.122 Read from
14 AWG copper 14 AWG copperthe 15 A device — the table’s first row
12 AWG copper (oversized circuit) 14 AWG copperstill the 15 A device — the EGC follows the breaker, not the conductor

The Ground Is the Same Size as the Conductor

At 15 amperes the equipment grounding conductor and the circuit conductor are both 14 AWG copper, which is why 14/2 NM-B carries a full-size bare ground rather than something thinner. The same thing happens at 20 and 30 amperes — 12 AWG with a 12 AWG ground, 10 AWG with a 10 AWG ground — and nowhere above them. The coincidence tracks the small-conductor range exactly: Table 250.122's first three rows name the very conductors NEC 240.4(D) caps, so wherever that provision reaches, the ground matches the conductor. It also means the table reads from the device rather than from the conductor: oversize the circuit to 12 AWG and the breaker is still 15 amperes, so the grounding conductor stays at 14 AWG.

One exception is worth knowing. NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally where the circuit conductors are upsized for voltage drop. Cable assemblies handle this themselves; individual conductors in conduit do not.

Cable Types for a 15 Amp Circuit

14/2 NM-B is the ordinary answer: two insulated 14 AWG conductors and a bare 14 AWG ground. 14/3 adds a third insulated conductor for a switched-and-constant pair, a three-way switch traveller, or a two-pole 240 volt circuit that needs a neutral. Since around 2001 the jacket colour tells you which gauge you are holding: 14 AWG NM-B is white, 12 AWG is yellow.

Why 334.80 Changes Nothing Here

NEC 334.80 holds non-metallic sheathed cable to the 60°C ampacity column whatever its conductors are individually rated. On several larger pages that rule is what decides the conductor. Here the arithmetic runs out flat:

  • 334.80 points at the 60°C column, where 14 AWG copper is 15 amperes.
  • NEC 240.4(D)(3) caps the device at 15 amperes.
  • The standard rating fitted is 15 amperes.

All three are the same number, so there is nothing to reconcile. It also makes this page unusually stable against a code revision: if 334.80 were narrowed so that NM-B read the 75°C column, 14 AWG would show 20 amperes — and 240.4(D)(3) would still hold the breaker at 15. The answer would not move.

The 240 Volt Case

A 15 ampere 240 volt circuit takes the same 14 AWG copper. Ampacity is a function of current and temperature, not of voltage, so the conductor does not change — a point worth stating plainly, because the 220, 230 and 240 volt phrasings are the largest voltage group in this page's search data and they are all the same circuit.

Two things do change. The breaker is two-pole rather than single-pole, occupying two slots and switching both ungrounded conductors together. And the 3 percent allowance is measured against 240 volts rather than 120, so the same 14 AWG reaches roughly twice as far — about 80 feet instead of 40. Where the circuit needs a neutral as well, 14/3 is the cable.

Insulation types and temperature ratings are covered on the wire sizes explained page. Conduit sizing comes from the fill tables in NEC Chapter 9.

Common Mistakes on 15 Amp Circuits

Swapping a Tripping 15 Amp Breaker for a 20

The most consequential error at this rating, and it is a one-minute job that leaves a permanent fault. A 15 ampere breaker on 14 AWG trips because the circuit is overloaded or faulted; fitting a 20 removes the protection rather than the problem, and NEC 240.4(D)(3) forbids it outright. The breaker is the wrong component to change. Find out what is drawing the current.

Reading the 75°C or 90°C Column

14 AWG copper genuinely carries 20 amperes at 75°C and 25 at 90°C, so a reader sizing on ampacity alone concludes it is a 20 ampere conductor and is reading the table correctly. The ampacity is not the permitted device. Those two numbers answer different questions, and at this rating only one of them decides the breaker.

Extending a 20 Amp Circuit with 14 AWG

An existing 12 AWG 20 ampere circuit gets lengthened with whatever is on the van, which leaves a 20 ampere circuit containing a 14 AWG segment protected at 20. The segment is the weakest point and the breaker cannot see it. If the cable is already in, fitting a 15 ampere breaker makes the circuit correct and reduces its capacity, which is the right answer where the circuit serves lighting or general receptacles.

Assuming 15 Amperes of Usable Load

A 15 ampere circuit is not 15 amperes of appliance. Continuous loads are sized at 125 percent, which is the same thing said from the other side — a circuit expected to run at its limit for three hours or more needs headroom designed in rather than discovered.

Treating 40 Feet as a Long Run

It is not long by any ordinary standard, and it is where 14 AWG at a full 15 amperes passes 3 percent drop. The conductor stays legal — the NEC's voltage-drop figures are advisory — but lights dim and motors start harder. This is the one place on this page where the thin conductor, rather than the rule, is the constraint.

Looking for an Aluminum Option

There is not one. NEC Table 310.16 starts its aluminum rows at 12 AWG, so there is no 14 AWG aluminum conductor to consider at all. 12 AWG aluminum exists and is capped at 15 amperes by NEC 240.4(D)(4), which makes it a legal if unusual way to serve a 15 ampere circuit.

Ignoring Derating in a Hot Space or a Bundle

The cap applies after correction factors, not instead of them. A cable run through an attic above 30°C, or bundled with more than three current-carrying conductors, is working from a reduced ampacity — and 14 AWG has the least room of any size to give up.

Frequently Asked Questions

The questions this page's search data carries, answered in one sentence each before any qualification. Two are editorial additions, marked in place.

What size wire do I need for a 15 amp breaker?

14 AWG copper. NEC Table 310.16 rates 14 AWG copper at 15 amperes in the 60°C column, which NEC 110.14(C)(1)(a) makes the default at this rating, and NEC 240.4(D)(3) caps its overcurrent device at 15 amperes as well. Both routes give the same conductor.

Can you use 12 AWG wire on a 15 amp breaker?

Yes. Nothing requires a conductor to match its breaker — the breaker protects the conductor, so a larger conductor on a 15 ampere device is protected further below its capacity and is always permitted. It is worth doing on a long run, where voltage drop rather than ampacity decides the size. Editorial addition — no keyword in this page's data asks this, and it is included on code grounds.

Can you use 14 AWG wire on a 20 amp breaker?

No. NEC 240.4(D)(3) limits the overcurrent device on 14 AWG copper to 15 amperes whatever the ampacity table says. The 20 amp wire size page works that case through from a 20 amp starting point.

What size wire for a 15 amp 240 volt circuit?

The same 14 AWG copper. Ampacity depends on current and temperature, not on voltage, so a 15 ampere circuit takes 14 AWG at 120 volts and at 240 volts alike. What changes is a two-pole breaker and that the same run is half the percentage voltage drop.

What size ground wire for a 15 amp circuit?

14 AWG copper, or 12 AWG aluminum, from NEC Table 250.122 read at the 15 ampere device. At this rating the equipment grounding conductor is the same size as the circuit conductor, as it also is at 20 and 30 amperes and at no rating above them.

How far can 14 AWG run on a 15 amp circuit?

About 40 feet one way at a full 15 amperes on 120 volts before the drop reaches 3 percent, and about 50 feet at the 12 amperes a general-purpose circuit is more likely to carry. That is the shortest reach of any rating on this site, and it is the one place the thin conductor rather than the rule is the constraint.

Is 14/2 or 14/3 cable right for a 15 amp circuit?

14/2 for an ordinary circuit — two insulated 14 AWG conductors and a bare 14 AWG ground. 14/3 adds a third insulated conductor and is for a switched-and-constant pair, a three-way switch traveller, or a two-pole 240 volt circuit that needs a neutral.

Does the 83 percent dwelling allowance apply to a 15 amp circuit?

No. NEC 310.12 reaches services and feeders rated 100 through 400 amperes, so a 15 ampere circuit is sized against the full 15 amperes from Table 310.16. The calculator on this page says so by name if you tick its dwelling-service control at this rating rather than silently doing nothing. Editorial addition — included because readers arrive here from the larger pages.

Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions. The 15 ampere limit on the overcurrent device is NEC 240.4(D)(3), whose subsection was checked against the enumeration in the primary text rather than against a secondary summary; the standard overcurrent ratings are NEC 240.6(A), and the equipment grounding conductor is from NEC Table 250.122. Voltage drop figures are computed from NEC Chapter 9 Table 9. These figures are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.