A 200 amp dwelling service needs 4/0 aluminum or 2/0 copper — but a 200 amp feeder to a sub-panel needs 250 kcmil aluminum or 3/0 copper, one size larger in each metal.

Aluminum comes first on this page because aluminum is what gets installed at this size: service-entrance cable and underground distribution conductors are predominantly aluminum at 200 amps, and 4/0 aluminum is the single most-quoted conductor in residential wiring. It is also right for only one of the two cases above. This page gives both answers and the provision that separates them, all three grounding conductors a 200 amp service needs, which cable types are real at this size, and how far the run can go. For how conductor sizing works as a subject, see wire sizes explained.

Check the Drop on Your Own 200 Amp Run

What This Calculator Is Set To

A 200 amp dwelling service in 4/0 aluminum — 200 amps, 240 volts, 4/0 aluminum, at the site's standard 75°C terminations. Set your own one-way distance and read the percentage.

Solve for

You know your wire size. Find out how much voltage you'll lose.

Conductor material
Circuit type

Advanced options
Calculation method
Installation type
About installation type

Steel conduit increases voltage drop on AC circuits. If you're not sure, leave this on PVC.

Conductor temperature
About conductor temperature

The insulation's temperature rating, printed on the wire. 75°C covers most installations.

About dwelling services and main feeders

The whole electrical supply to a house or apartment, sized 100–400 amps. Not a sub-panel. Lets the conductor be sized to 83% of the rating, as the NEC allows for this case only — assuming no derating for ambient temperature or conductor count, which this calculator does not check.

About parallel sets per phase

Only if you're running more than one conductor per phase. Most circuits use 1.

About power factor

How much of the current does useful work. Motors are around 0.8, resistive loads are 1.0. Leave at 0.9 if unsure.

0.1 – 1.0

Percentage drop

0.9%

Voltage drop

2.16 V

Voltage at the load

237.84 V

R used, Ω/1000 ft

0.100

X used, Ω/1000 ft

0.0410

Under 3% Fine for a branch circuit — no action needed

How this was calculated
  1. Source: NEC Chapter 9, Table 9 — AC resistance and reactance, 75 °C
  2. R at 75 °C = 0.100 Ω/1000 ft (4/0 AWG aluminum, PVC conduit or direct burial)
  3. X = 0.0410 Ω/1000 ft (PVC conduit or direct burial)
  4. Power factor 0.90: cos θ = 0.900, sin θ = 0.436
  5. Z = R·cos θ + X·sin θ = 0.100 × 0.900 + 0.0410 × 0.436 = 0.108 Ω/1000 ft
  6. Z is computed from R and X by Table 9 note 2 at the power factor above, not read from the table’s effective-Z columns, which hold only at 0.85.
  7. Vd = 2 × I × L × Z ÷ 1000 ÷ sets
  8. Vd = 2 × 200 A × 50.0 ft × 0.108 ÷ 1000 ÷ 1 = 2.16 V
  9. Drop = 2.16 V ÷ 240 V × 100 = 0.9%
  10. Voltage at the load = 240 − 2.16 = 237.84 V

What Size Wire for a 200 Amp Service?

A 200 amp dwelling service takes 4/0 aluminum or 2/0 copper. NEC 310.12 permits the service conductors supplying the entire load of a one-family dwelling, or of an individual dwelling unit, to have an ampacity of not less than 83 percent of the service rating — 166 amperes on a 200 amp service — and NEC Table 310.16 rates 4/0 aluminum at 180 amperes and 2/0 copper at 175 amperes on 75°C terminations. Both clear 166.

Why the Allowance Exists, and What It Assumes

The 83 percent figure is not a safety margin being spent. A dwelling's service conductors never carry the connected load, because a house does not run its range, dryer, water heater and air conditioning simultaneously, and NEC 310.12 encodes that diversity as a permitted reduction rather than requiring every installer to compute it. The allowance is conditioned on the conductors being rated 75°C or better and on no correction or adjustment factor being required, and it reaches only services and feeders rated 100 through 400 amperes.

The Sub-Panel Feeder Answer: 250 kcmil or 3/0 Copper

A 200 amp feeder to a sub-panel needs 250 kcmil aluminum or 3/0 copper, sized against the full 200 amperes from NEC Table 310.16. The allowance turns on the words "the entire load": a feeder that carries part of a dwelling's load gets no reduction, however it is wired and whatever its rating. 250 kcmil aluminum is rated 205 amperes and 3/0 copper exactly 200.

3/0 copper sitting precisely on 200 amperes is the one figure on this page worth pausing over. It is not a conductor running out of margin. Table 310.16's ampacities are the current a conductor carries continuously at its insulation's rated temperature in the conditions the table assumes, and a conductor at its tabulated ampacity is operating exactly as designed. What removes the margin is not the number but the conditions: a high ambient temperature or more than three current-carrying conductors in the raceway requires a correction or adjustment factor, and applied to 200 amperes that drops 3/0 below the rating with nothing in reserve. On a 200 amp feeder in a hot attic or a crowded raceway, 4/0 copper is the conductor that survives the arithmetic.

Single-Phase Only

NEC 310.12 applies to single-phase dwelling services and feeders, so a 200 amp three-phase service gets no reduction and is sized against the full rating. The calculator declines the allowance by name when the circuit is set to three-phase rather than applying it silently.

How Far a 200 Amp Service Can Run

A 200 amp service in 4/0 aluminum holds 3 percent voltage drop to 216 feet and 5 percent to 361 feet, one way. The table below gives the ladder for all three conductors this page recommends.

Voltage drop on a 200 amp run at 240 volts, single-phase
One-way run 4/0 aluminum, service 250 kcmil aluminum, feeder 2/0 copper, service
50 ft 0.69%0.71%0.69%
100 ft 1.38%1.42%1.38%
150 ft 2.08%2.13%2.08%
200 ft 2.77%2.83%2.77%
250 ft 3.46%3.54%3.46%
300 ft 4.15%4.25%4.15%
400 ft 5.53%5.67%5.53%

At 300 feet — the distance readers ask about most — a 200 amp service in 4/0 aluminum runs 4.15 percent, which is inside the 5 percent total that the informational note to NEC 210.19(A) describes as reasonable but past the 3 percent it suggests for a feeder. Upsizing one step to 300 kcmil aluminum holds 3 percent to 305 feet, and 4/0 copper reaches 349 feet.

Two things about that table are worth saying plainly. The service conductor and the sub-panel conductor reach almost the same distance despite differing by a trade size, because the smaller conductor is carrying proportionally less current and the two effects very nearly cancel. And voltage drop is a recommendation throughout — the informational notes to NEC 210.19(A) and 215.2(A) are not enforceable requirements, while ampacity is. A conductor can be fully code-compliant and still deliver poor voltage at the far end.

Underground and Overhead Service Conductors

An underground service lateral is normally 4/0 aluminum USE-2 or aluminum underground distribution cable, direct buried at the depth NEC Table 300.5(A) requires for the wiring method and location. An overhead service drop is the utility's responsibility up to the point of attachment, and the service-entrance conductors from there to the disconnect are the installer's. NEC 230.42(A) requires those conductors to have an ampacity not less than the load calculated under Article 220, and not less than the rating of the service disconnect — which is the provision NEC 310.12's 83 percent allowance is read against, and the two interact in a way covered further down this page.

200 Amp Wire Size Chart

This chart gives every conductor near a 200 amp rating against both cases, because at 200 amps the case decides the answer and a single column cannot express it.

Both Cases, Side by Side

Conductors for a 200 amp service and a 200 amp sub-panel feeder, NEC Table 310.16 at 75°C
Conductor Dwelling service or whole-dwelling feeder Sub-panel feeder Ampacity at 75°C
1/0 aluminum No — 46 A shortNo120 A
3/0 aluminum No — 11 A shortNo155 A
4/0 aluminum Yes — 310.12, 83%No — 20 A short180 A
250 kcmil aluminum Yes, oversizedYes — the standard answer205 A
1/0 copper No — 16 A shortNo150 A
2/0 copper Yes — 310.12, 83%No — 25 A short175 A
3/0 copper Yes, with marginYes — exactly 200 A200 A
4/0 copper Yes, oversizedYes, with margin230 A

In short: 4/0 aluminum and 2/0 copper serve a 200 amp dwelling service under NEC 310.12's 83 percent allowance, while a 200 amp sub-panel feeder needs 250 kcmil aluminum or 3/0 copper against the full rating. Every figure in the ampacity column is the 75°C value from NEC Table 310.16, which is the column NEC 110.14(C) requires at the termination ratings of virtually all residential equipment.

Why the 90°C Column Is Not the Answer

The 90°C column is the one readers most often reach for by mistake. It would make 1/0 copper sufficient for the service case at 170 amperes, and 110.14(C) forecloses it: a conductor's ampacity is limited to the lowest temperature rating of any connected termination, and a 200 amp residential panel and meter socket are listed for 75°C. The 90°C rating on the conductor's insulation is real and it is used for derating calculations, not for picking the conductor off the table.

Grounding a 200 Amp Service

"Ground wire size for a 200 amp service" has four answers, because a 200 amp service has four conductors that could be meant: a grounding electrode conductor, the shortened version of it that runs to a ground rod, an equipment grounding conductor, and the grounded conductor most people call the neutral. They are sized by three different rules and they are not the same size.

Grounding conductors for a 200 amp service, NEC Tables 250.66 and 250.122
Service conductor Grounding electrode conductor Max required to a ground rod Equipment grounding conductor
4/0 aluminum (service) 4 AWG copper or 2 AWG aluminum6 AWG copper or 4 AWG aluminum6 AWG copper or 4 AWG aluminum
250 kcmil aluminum (feeder) 4 AWG copper or 2 AWG aluminum6 AWG copper or 4 AWG aluminum6 AWG copper or 4 AWG aluminum
2/0 copper (service) 4 AWG copper or 2 AWG aluminum6 AWG copper or 4 AWG aluminum6 AWG copper or 4 AWG aluminum
3/0 copper (feeder) 4 AWG copper or 2 AWG aluminum6 AWG copper or 4 AWG aluminum6 AWG copper or 4 AWG aluminum

Reading across any row: the grounding electrode conductor for a 200 amp service is 4 AWG copper, the portion of it that is the sole connection to a ground rod need not exceed 6 AWG copper, and the equipment grounding conductor is 6 AWG copper. Every row of that table is identical, which is the useful finding — at 200 amps the choice between the service answer and the sub-panel answer changes the service conductor and changes none of the grounding conductors.

The Grounding Electrode Conductor

The grounding electrode conductor for a 200 amp service is 4 AWG copper or 2 AWG aluminum, from NEC Table 250.66. That table is read from the size of the largest ungrounded service-entrance conductor — or the equivalent circular-mil area where the service runs in parallel sets — and not from the service rating. 2/0 copper, 3/0 copper, 4/0 aluminum and 250 kcmil aluminum all fall in the same row of Table 250.66, which is why all four conductor answers on this page produce the same grounding electrode conductor.

That the table is keyed to conductor size rather than to amperes is the part most often got wrong, and it matters more here than at any other rating: a 200 amp service is the one rating where the same installation legitimately has two different ungrounded conductor sizes depending on which case it is.

The Ground Rod Exception

Where the grounding electrode conductor's sole connection is to a rod, pipe or plate electrode, NEC 250.66(A) states it is never required to be larger than 6 AWG copper or 4 AWG aluminum — two sizes below the 4 AWG the table gives, on the largest service most houses will ever have. NEC 250.66(B) caps the conductor to a concrete-encased electrode at 4 AWG copper, and NEC 250.66(C) caps the conductor to a ground ring at the size of the ring itself.

This reads like the code contradicting itself and it does not. Table 250.66 sets a minimum; 250.66(A) sets a ceiling on one particular run. A driven rod has a high and variable resistance to earth that a larger conductor does nothing to improve, so the code stops requiring copper that buys nothing. The distinction worth holding onto is the same one that separates a conductor's ampacity from its permitted breaker size: two provisions can govern the same conductor and answer different questions.

The cap applies to that portion only. A grounding electrode conductor that serves a rod and continues to a metal water pipe or a concrete-encased electrode is not the sole connection to the rod, and the unspliced run is back to 4 AWG copper. Sizing the whole conductor at 6 AWG because a rod is in the system is the mistake this exception produces.

The Equipment Grounding Conductor

The equipment grounding conductor for a 200 amp feeder is 6 AWG copper or 4 AWG aluminum, from NEC Table 250.122 against the rating of the overcurrent device — not against the conductor size and not from the ampacity table. 200 amperes is one of the few ratings with its own row in Table 250.122, so the figure is read directly rather than rounded up to the next listed rating.

Where the ungrounded conductors are increased in size for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally. A 300-foot feeder upsized from 250 kcmil to 350 kcmil aluminum carries an equipment grounding conductor larger than the 4 AWG the table lists.

The Neutral Is a Separate Calculation

The grounded conductor — the neutral — is the larger of two numbers, so it is a calculation rather than a lookup. NEC 220.61 sizes it for the maximum unbalanced load, which is the maximum net calculated load between the neutral and any one ungrounded conductor. NEC 250.24(C)(1) then sets a floor from Table 250.102(C)(1), which for a 200 amp service's conductors is 4 AWG copper or 2 AWG aluminum. Whichever is larger governs.

NEC 310.12(D) permits the grounded conductor to be smaller than the ungrounded conductors where 220.61 and 230.42 are satisfied, and readers are routinely surprised by that. A 200 amp service in 4/0-4/0-4/0-2/0 aluminum service-entrance cable has a neutral two sizes below its ungrounded conductors, and it is correct: the 240 volt loads that dominate a modern dwelling — range, dryer, water heater, air conditioning, an EV charger — put no current on the neutral at all, so the unbalanced load is a fraction of the service rating.

Note the subsection. The permission is NEC 310.12(D) in NFPA 70-2023; 310.12(C) is a different provision, and the two are easy to transpose because the 2026 edition relocates the correction-and-adjustment sentence that 310.12(D) also carries.

Wire Size for a 200 Amp Sub-Panel

A 200 amp sub-panel feeder takes 250 kcmil aluminum or 3/0 copper, sized against the full 200 amperes because NEC 310.12's 83 percent allowance reaches only conductors supplying a dwelling's entire load.

When a Panel at 200 Amps Is Actually the Service

Most searches for a "200 amp panel" are about the main panel of a house, which is fed by service conductors and takes the service answer — 4/0 aluminum or 2/0 copper. A 200 amp sub-panel in a dwelling is genuinely unusual, because a sub-panel that large is normally fed from a service of 400 amperes or more. If the panel is the one the meter feeds, it is the service case whatever it is called.

A Feeder to a Detached Structure

A 200 amp feeder to a detached building is sized the same way, and NEC 250.32 governs its grounding: the structure needs its own grounding electrode system, and the equipment grounding conductor runs with the feeder rather than relying on a bonded neutral at the far end. This case drives a large part of the 60- and 100-amp pages and almost none of this one, which is itself informative — at 200 amperes the question is nearly always the house's own supply.

Cable Types for a 200 Amp Service

A 200 amp service is wired in service-entrance cable, individual conductors in conduit, or underground cable — SEU from the meter, SER for an interior feeder, THHN in conduit, and USE-2 or underground distribution cable for a lateral.

NM-B Is Not Made This Large

NM-B is not a candidate at 200 amperes, and not because of its temperature limitation. The cable is manufactured in 14, 12, 10, 8, 6, 4 and 2 AWG, and a 200 amp service needs 4/0 aluminum or 2/0 copper. There is no 200 amp NM-B answer to evaluate.

SEU — From the Meter to the Disconnect

Type SEU is the flat, two-conductor-plus-concentric-neutral cable that runs from the meter socket to the service disconnect. Sized as service-entrance conductors under Article 230 at the 75°C column, 4/0 aluminum SEU serves a 200 amp dwelling service. SEU has no separate equipment grounding conductor — its concentric neutral is the grounded conductor — so it cannot serve as a four-wire feeder downstream of the disconnect however convenient its profile is.

SER — Where the 60°C Limit Does Not Apply

Type SER is the four-conductor round cable used as an interior feeder from a service disconnect to a panel, and 4/0-4/0-4/0-2/0 aluminum SER serves a 200 amp dwelling service or whole-dwelling feeder. That answer depends on a single exclusion, and it is the one fact on this page most likely to be contradicted by another source.

NEC 338.10(B)(4)(a) requires Type SE cable used for interior wiring to comply with the installation requirements of Part II of Article 334 — excluding 334.80. NEC 334.80 is the provision that holds NM-B to the 60°C column of Table 310.16, and it is named and excluded. The 60°C ampacity rule that 338.10(B)(4)(a) does impose reaches only ungrounded conductors 10 AWG and smaller installed in thermal insulation. A 4/0 aluminum conductor is neither, so SER at this size is a 75°C conductor rated 180 amperes.

This inverts the answer on every smaller circuit, and the inversion is the point. At 30, 40, 50, 60 and 100 amperes the 60°C limitation is the provision that decides the conductor, and a cable answer is routinely a size larger than the conduit answer for exactly that reason. At 200 amperes the same family of rules reaches the opposite result, because the cable is a different article and that article excludes the limitation by name.

USE-2 for an Underground Lateral

Type USE-2 is the conductor for a direct-buried service lateral, rated 90°C wet and dry, and 4/0 aluminum USE-2 serves a 200 amp dwelling service at the 75°C termination column. USE is not permitted inside a building beyond the point of entrance, so a lateral transitions to another wiring method at or near the service equipment. Aluminum underground distribution cable is the same conductor in a triplex or quadruplex assembly and is what most utilities install.

THHN in Conduit

Individual THHN conductors in conduit are the usual choice where the service runs through a mast, a long riser or a finished wall. THHN is rated 90°C dry, and in the wet locations a service raceway counts as it is dual-rated THHN/THWN-2 and used at 75°C. The conductor is 4/0 aluminum or 2/0 copper for a service, and conduit sizing comes from the fill tables in NEC Chapter 9 rather than from anything on this page.

Aluminum or Copper at 200 Amps?

Aluminum, for almost every 200 amp residential service. This page leads with aluminum on practical rather than search grounds — the two metals are searched almost equally often at this rating, but aluminum is what is actually installed, because service-entrance cable and underground distribution conductors are predominantly aluminum at 200 amperes and the copper equivalent costs several times as much for no gain the installation can use.

Aluminum: 4/0 for a Service, 250 kcmil for a Feeder

4/0 aluminum is rated 180 amperes at 75°C and serves a 200 amp dwelling service under NEC 310.12. 250 kcmil aluminum is rated 205 amperes and serves a 200 amp sub-panel feeder at the full rating. Aluminum building wire at these sizes is AA-8000 series alloy, which is what makes it suitable for the terminations it lands on — the 1970s problems with aluminum branch-circuit wiring concerned a different alloy in 12 and 10 AWG, and have no bearing on 4/0 service conductors.

Copper: 2/0 for a Service, 3/0 for a Feeder

2/0 copper is rated 175 amperes at 75°C and serves a 200 amp dwelling service; 3/0 copper is rated exactly 200 amperes and serves a feeder at the full rating. Copper is worth its cost at 200 amperes in two situations: where conduit fill or an existing raceway makes the smaller conductor diameter decisive, and where terminations are listed for copper only.

A note on a comparison that looks cleaner than it is. 2/0 copper and 4/0 aluminum have close enough resistance — 0.0967 against 0.100 ohms per 1,000 feet in NEC Chapter 9 Table 8 — that voltage drop almost never decides between them; the figures differ by about 3 percent, which no installation will notice. The choice is made on cost, on conductor diameter and on what the lugs are listed for, not on performance.

Terminations, Antioxidant and Torque

At 4/0 the termination is where aluminum installations fail, not the conductor. Three things matter and all three are code or listing requirements rather than good practice. Lugs must be marked AL or AL/CU — a CU-only lug on aluminum is a violation of NEC 110.14 regardless of how well it is made. Terminations must be torqued to the value marked on the equipment or given in its instructions, which NEC 110.14(D) requires be done with a calibrated tool. And where the listing calls for a contact-aid compound, it must be used; where it does not, adding one is not an improvement.

Is 200 Amps Enough?

For most houses, yes — 200 amperes is the standard modern residential service and comfortably covers a dwelling with gas heat, a conventional range and one car. Whether it covers a particular house is answered by an Article 220 load calculation and by nothing else, including the square footage rules of thumb that circulate in its place.

What Pushes a Dwelling Past 200 Amps

Electrification is what exhausts a 200 amp service, and it does so through a small number of large continuous loads. An electric vehicle charger is calculated as a continuous load at 125 percent under NEC 625.42, so a 48 amp charger is 60 amperes of calculated demand before anything else is counted. A second charger doubles it. Electric resistance heat, a heat pump with resistance backup, an induction range and a heat-pump water heater each add materially, and a house taking several of them at once is the normal case for a service upgrade.

For an existing dwelling adding load, NEC 220.83 is the calculation that matters: 100 percent of the first 8 kVA of the existing load plus 40 percent of the remainder, with new air conditioning or electric space heating added at 100 percent. If the total exceeds the service rating, the service is undersized for the new load — and that is a finding about the service, not about the conductors, which are already correct for 200 amperes.

Load Management Instead of a Service Upgrade

The answer to a 200 amp service that no longer fits is often an energy management system rather than a larger service, and the code now says so directly. NEC 220.70 permits the setpoint of an energy management system to be used as the calculated load for the circuits it controls, and NEC 750.30 governs how such a system must behave. A controller that prevents an EV charger and an electric range from drawing simultaneously lets a 200 amp service carry loads that would otherwise require 400 amperes, and it costs a fraction of a service upgrade — which at 200 to 400 amperes means a new meter base, a new panel, a new grounding electrode system and usually utility work.

Readers arriving here from a smaller existing service should note that the rating below this one behaves differently in one respect worth knowing: at 150 amperes all four grounding and bonding rules return the same conductor, which they do not here. See 150 amp wire size.

Where the calculation genuinely does not fit, a 400 amp service is the usual next step and its conductors are a different subject: at that rating parallel sets are normal, the 83 percent allowance lands on conductor sizes above those this site publishes, and the grounding electrode conductor moves to a different row of Table 250.66.

Why Other Sources Give Different Numbers

Cross-checking a 200 amp service will turn up two figures that contradict this page, and both disagreements have identifiable causes rather than one source being careless.

"4/0 Aluminum SER Is Only Good for 150 Amps"

This was true, under the 2008 NEC. That edition deleted the words "excluding 334.80" from 338.10(B)(4), which pushed Type SE cable used for interior wiring to the 60°C column of the ampacity table, where 4/0 aluminum is 150 amperes. The 2011 edition restored the exclusion and it has stood since. So a source stating 150 amperes is not inventing a figure; it is quoting a code cycle that ended in 2011, and the figure was correct when it was written.

The practical consequence is that the edition matters more than the source's reputation. Under NFPA 70-2023, 4/0 aluminum SER on an interior feeder is 180 amperes. Check which edition your jurisdiction has adopted, and check whether it has amended Article 338 — this is a provision local amendments have targeted.

Whether the 83 Percent Allowance Survives NEC 230.42(B)

Some sources size a 200 amp service at 3/0 copper or 250 kcmil aluminum — the full-rating figures — and they are being deliberately conservative rather than wrong. NEC 310.12(A) permits 83 percent of the rating, while NEC 230.42(A) requires service-entrance conductors to have an ampacity not less than the load calculated under Article 220 and not less than the rating of the service disconnect. Whether 310.12's permission can be read against 230.42(B) as the sections are currently worded is an open question among code professionals, and the 2026 edition carries a clarification of it.

This page gives the 310.12 figures because they are what the provision permits and what is installed, and names the tension because a reader who meets it from an inspector should not meet it for the first time there. Sizing a 200 amp service at 250 kcmil aluminum is never a violation — it is larger than required — so an installer who prefers the full-rating conductor has given up money and nothing else.

Where Our Own Figures Come From

Every ampacity on this page is the 75°C column of NEC Table 310.16 as published in NFPA 70-2023, verified against independent reproductions cell by cell. The grounding figures come from Table 250.66 and Table 250.122, verified the same way. Where a figure could not be verified to that standard it is not on this page: the grounded-conductor floor is given for the 75°C case only, and no figure is published for a service run in parallel sets.

Common Mistakes on 200 Amp Services

Using 4/0 Aluminum for Everything at 200 Amps

4/0 aluminum is the correct conductor for a 200 amp dwelling service and it is 20 amperes short as a 200 amp sub-panel feeder. It is the most quoted figure in residential wiring and it is quoted without its condition more often than with it. The condition is that the conductors supply the dwelling's entire load.

Applying the 83 Percent Allowance to a Partial-Load Feeder

NEC 310.12 reaches conductors supplying the entire load associated with a dwelling unit. A 200 amp feeder to a sub-panel that carries some of the house gets no reduction, and a feeder to a detached garage gets none either. This is the error on this page's own subject most likely to produce an undersized installation.

Sizing the Whole Grounding Electrode Conductor at 6 AWG

NEC 250.66(A) caps the conductor whose sole connection is to a rod, pipe or plate electrode. Where the same conductor continues to a metal water pipe or a concrete-encased electrode, the unspliced run is 4 AWG copper. The inverse error is just as common: reading 4 AWG off Table 250.66 and running it to a rod that never required more than 6 AWG.

Sizing the Neutral from the Table Alone

Table 250.102(C)(1) gives a floor of 4 AWG copper, and NEC 220.61 gives the maximum unbalanced load. The neutral is the larger of the two, and a service with substantial 120 volt load can need a neutral well above the floor. Quoting the table by itself answers half the question.

Reading the 90°C Column

1/0 copper is rated 170 amperes at 90°C, which clears the 166 amperes a 200 amp dwelling service requires, and it is not a legal answer. NEC 110.14(C) limits the conductor to the lowest-rated termination in the circuit, and a residential meter socket and panel are listed for 75°C.

Treating Voltage Drop as a Requirement, or Ignoring It

The 3 percent figure comes from informational notes to NEC 210.19(A) and 215.2(A) and is a recommendation, not an enforceable limit. Ampacity is the requirement. Both errors are common at this rating — failing a compliant 300-foot service for 4.15 percent drop, and running one at 5.5 percent because the conductor satisfies the table.

Frequently Asked Questions

What size wire for a 200 amp service?

A 200 amp dwelling service takes 4/0 aluminum or 2/0 copper. NEC 310.12 permits service conductors supplying the entire load of a one-family dwelling to be sized at 83 percent of the rating, which is 166 amperes, and those two conductors carry 180 and 175 amperes at 75°C. A 200 amp feeder to a sub-panel does not qualify and needs 250 kcmil aluminum or 3/0 copper.

What size aluminum wire for a 200 amp service?

4/0 aluminum, for a dwelling service. It is rated 180 amperes at 75°C, which clears the 166 amperes NEC 310.12 requires at 83 percent of a 200 amp rating. This is the figure most sources quote for a 200 amp service, and it is correct only for the service or whole-dwelling feeder case — a sub-panel feeder needs 250 kcmil.

What size copper wire for a 200 amp service?

2/0 copper, for a dwelling service, rated 175 amperes at 75°C against the 166 amperes NEC 310.12 requires. Copper is uncommon at this size because the aluminum equivalent costs far less and performs almost identically. A 200 amp sub-panel feeder in copper needs 3/0, which Table 310.16 rates at exactly 200 amperes.

What size ground wire for a 200 amp service?

It depends which grounding conductor you mean, and a 200 amp service has three. The grounding electrode conductor is 4 AWG copper from NEC Table 250.66. Where it is the sole connection to a ground rod, NEC 250.66(A) caps it at 6 AWG copper. The equipment grounding conductor is 6 AWG copper from NEC Table 250.122.

What size ground rod wire for a 200 amp service?

6 AWG copper, or 4 AWG aluminum. NEC 250.66(A) states that where the grounding electrode conductor's sole connection is to a rod, pipe or plate electrode, it is never required to be larger than that — two sizes below the 4 AWG the table gives. The cap applies only to that portion; a conductor continuing to a water pipe or concrete-encased electrode is back to 4 AWG.

What size neutral wire for a 200 amp service?

The neutral is the larger of two numbers, so it is a calculation rather than a lookup. NEC 220.61 sizes it for the maximum unbalanced load, and NEC 250.24(C)(1) sets a floor of 4 AWG copper from Table 250.102(C)(1). NEC 310.12(D) permits it smaller than the ungrounded conductors, which is why a 200 amp service often runs a reduced neutral.

What size SER cable for a 200 amp service?

4/0-4/0-4/0-2/0 aluminum SER serves a 200 amp dwelling service or whole-dwelling feeder. Despite what many sources say, SER used as interior wiring is not held to the 60°C column: NEC 338.10(B)(4)(a) requires compliance with Part II of Article 334 excluding 334.80, so 4/0 aluminum is a 75°C conductor at 180 amperes.

Is 4/0 aluminum really enough for a 200 amp service?

Yes, for a dwelling service or a feeder carrying a whole dwelling's load. 4/0 aluminum carries 180 amperes at 75°C, below the 200 amp rating, and that is permitted only because NEC 310.12 lowers the requirement to 166 amperes. Used as a 200 amp sub-panel feeder, where the allowance does not reach, 4/0 aluminum is 20 amperes short.

What size wire for a 200 amp sub panel?

250 kcmil aluminum or 3/0 copper. A sub-panel feeder carries part of a dwelling's load, so NEC 310.12's 83 percent allowance does not apply and the conductor is sized against the full 200 amperes from Table 310.16. That is one size larger than the service answer in each metal.

What size wire for a 200 amp service 300 feet away?

4/0 aluminum reaches 300 feet at 4.15 percent voltage drop, which is inside the 5 percent total that NEC 210.19(A)'s informational note describes but past the 3 percent it recommends for a feeder. Upsizing one step to 300 kcmil aluminum holds 3 percent to 305 feet. Ampacity does not change with length; only the drop does.

Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions; the 83 percent dwelling service allowance is NEC 310.12, and grounding conductors are from NEC Table 250.66, Table 250.102(C)(1) and Table 250.122. They are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.