A 125 amp dwelling service needs 2 AWG copper or 1/0 aluminum. A 125 amp feeder to a sub-panel needs 1 AWG copper or 2/0 aluminum — one size larger in each metal.

Which of those two you are wiring matters more at 125 amperes than at any other rating, and not only for the conductor. The grounding electrode conductor changes as well — 8 AWG copper for the service, 6 AWG for the feeder — because the code reads that table from the conductor's size rather than from the amperage, and at 125 amperes the two cases fall either side of a row boundary. This page gives both answers, every grounding conductor for each, why NM-B cable fails here by less than nine amperes, and what the number stamped on a panel label actually commits you to. For how conductor sizing works as a subject, see wire sizes explained.

Check the Drop on Your Own 125 Amp Run

What This Calculator Is Set To

A 125 amp dwelling service in 1/0 aluminum, 100 feet one way — 125 amperes, 240 volts, at the site's standard 75°C terminations. Set your own distance and read the percentage.

Solve for

You know your wire size. Find out how much voltage you'll lose.

Conductor material
Circuit type

Advanced options
Calculation method
Installation type
About installation type

Steel conduit increases voltage drop on AC circuits. If you're not sure, leave this on PVC.

Conductor temperature
About conductor temperature

The insulation's temperature rating, printed on the wire. 75°C covers most installations.

About dwelling services and main feeders

The whole electrical supply to a house or apartment, sized 100–400 amps. Not a sub-panel. Lets the conductor be sized to 83% of the rating, as the NEC allows for this case only — assuming no derating for ambient temperature or conductor count, which this calculator does not check.

About parallel sets per phase

Only if you're running more than one conductor per phase. Most circuits use 1.

About power factor

How much of the current does useful work. Motors are around 0.8, resistive loads are 1.0. Leave at 0.9 if unsure.

0.1 – 1.0

Percentage drop

2.1%

Voltage drop

4.98 V

Voltage at the load

235.02 V

R used, Ω/1000 ft

0.200

X used, Ω/1000 ft

0.0440

Under 3% Fine for a branch circuit — no action needed

How this was calculated
  1. Source: NEC Chapter 9, Table 9 — AC resistance and reactance, 75 °C
  2. R at 75 °C = 0.200 Ω/1000 ft (1/0 AWG aluminum, PVC conduit or direct burial)
  3. X = 0.0440 Ω/1000 ft (PVC conduit or direct burial)
  4. Power factor 0.90: cos θ = 0.900, sin θ = 0.436
  5. Z = R·cos θ + X·sin θ = 0.200 × 0.900 + 0.0440 × 0.436 = 0.199 Ω/1000 ft
  6. Z is computed from R and X by Table 9 note 2 at the power factor above, not read from the table’s effective-Z columns, which hold only at 0.85.
  7. Vd = 2 × I × L × Z ÷ 1000 ÷ sets
  8. Vd = 2 × 125 A × 100 ft × 0.199 ÷ 1000 ÷ 1 = 4.98 V
  9. Drop = 4.98 V ÷ 240 V × 100 = 2.1%
  10. Voltage at the load = 240 − 4.98 = 235.02 V

What Size Wire for a 125 Amp Service?

The wire size for a 125 amp service is 2 AWG copper or 1/0 aluminum. NEC 310.12 permits the service conductors supplying the entire load of a one-family dwelling, or of an individual dwelling unit, to have an ampacity of not less than 83 percent of the service rating. On a 125 amp service that is 103.75 amperes, and NEC Table 310.16 rates 2 AWG copper at 115 amperes and 1/0 aluminum at 120 amperes on 75°C terminations — margins of 11.25 and 16.25 amperes.

103.75 Amperes, and What the Calculator Does With It

The calculator sizes on 103.75 and rounds only the figure it prints, so its binding sentence reads 104 amperes while the conductor it returns is computed from 103.75. The three-quarters of an ampere cannot change an answer: NEC Table 310.16 publishes only whole numbers, so no ampacity can be both at least 103.75 and less than 104, and the smallest conductor clearing one is the conductor clearing the other in every column and both metals. The figure to work from is 103.75.

Three-Phase Gets No Reduction

NEC 310.12 applies to single-phase dwelling services and feeders, so a 125 amp three-phase service is sized against the full rating. The calculator declines the allowance by name when the circuit is set to three-phase rather than applying it silently.

How Far a 125 Amp Service Reaches

A 125 amp service in 1/0 aluminum holds 3 percent voltage drop to 216 feet one way; 2 AWG copper reaches 231 feet. At 150 feet — the one distance readers ask about on this rating — 1/0 aluminum runs 2.08 percent and 2 AWG copper 1.95 percent, both comfortably inside it. The 3 percent figure is a recommendation from the informational note to NEC 210.19(A) rather than an enforceable limit, and NEC 90.5(C) makes informational notes unenforceable; ampacity, which has no distance term, is the requirement.

Wire Size for a 125 Amp Sub-Panel

The wire size for a 125 amp sub panel is 1 AWG copper or 2/0 aluminum, sized against the full 125 amperes from NEC Table 310.16. A sub-panel feeder carries part of a dwelling's load, so NEC 310.12's allowance does not reach it — the allowance turns on the words "the entire load", and it does so regardless of how the feeder is run or what it is called.

1 AWG copper is rated 130 amperes and 2/0 aluminum 135 amperes, margins of 5 and 10 amperes over the rating. A 125 amp sub-panel 100 feet from the main panel runs 1.25 percent voltage drop in 1 AWG copper and 1.38 percent in 2/0 aluminum.

This Rating Is Asked About as a Feeder More Than Most

Included as market context rather than as a code requirement. Among the service-rated pages on this site, 125 amperes is the one whose readers ask about sub-panels most often — roughly two service questions for every sub-panel question, where at 150 and 200 amperes the ratio is fifteen and twenty-eight to one. 100 amperes behaves like 125 does; the change happens between 125 and 150.

Part of that has a code explanation, covered further down this page: NEC 408.36 lets a panelboard be rated above the feeder supplying it, so a 125 amp load centre is a normal thing to install where no conductor carries 125 amperes. Why the pattern breaks where it does is not something the code settles, and this page does not claim a cause it cannot show.

The Far End of a Sub-Panel Feeder

A sub-panel feeder is four conductors — two ungrounded, one grounded and one equipment grounding conductor. At the sub-panel the neutral bar and the ground bar are isolated from each other and the main bonding jumper is removed, because the grounded conductor and the equipment ground are bonded at one point only, the service disconnect. That is NEC 408.40 with 250.24(A)(5), and it is the same at every rating.

125 Amp Wire Size Chart

This chart gives every conductor near a 125 amp rating against both cases, because at this rating the case decides the answer and one column cannot carry it.

Both Code Paths Against the Ampacity

Conductors for a 125 amp service and a 125 amp sub-panel feeder, NEC Table 310.16 at 75°C
Conductor Dwelling service, 310.12 Sub-panel feeder Ampacity at 75°C
3 AWG copper No — 3.75 A shortNo100 A
2 AWG copper Yes — 310.12, 83%No — 10 A short115 A
1 AWG copper Yes, with marginYes — the standard answer130 A
1/0 copper Yes, oversizedYes, with margin150 A
2 AWG aluminum No — 13.75 A shortNo90 A
1/0 aluminum Yes — 310.12, 83%No — 5 A short120 A
2/0 aluminum Yes, oversizedYes — the standard answer135 A
3/0 aluminum Yes, oversizedYes, with margin155 A

In short: 2 AWG copper and 1/0 aluminum serve a 125 amp dwelling service under the 83 percent allowance, while a 125 amp sub-panel feeder needs 1 AWG copper or 2/0 aluminum against the full rating. Every ampacity shown is the 75°C value, which is the column NEC 110.14(C) requires at the termination ratings of virtually all residential equipment.

The near misses in that table are worth reading as carefully as the answers. 1/0 aluminum is five amperes short of a full 125 amp feeder and 3 AWG copper is under four amperes short of the service requirement — close enough that a reader working from a rounded figure can land on either and be wrong.

Why There Is No Maximum Breaker Column

NEC 240.4(D) does not reach these sizes. That provision caps the overcurrent device on 14, 12 and 10 AWG conductors only, and the smallest conductor a 125 amp circuit uses is 2 AWG. Readers arriving from smaller amperages expect it, because at 15, 20 and 30 amperes it is the rule that produces the answer. Here the ampacity table and NEC 310.12 decide it between them and there is no separate device limit to reconcile.

Grounding Splits by Case at 125 Amps

A 125 amp service takes an 8 AWG copper grounding electrode conductor and a 125 amp sub-panel feeder takes 6 AWG copper. Same rating, same house, two different answers — and the reason is that NEC Table 250.66 is read from the size of the conductor rather than from the amperage.

Grounding and bonding conductors for a 125 amp service and feeder, by the conductor each derives from
Case and its conductor GEC — Table 250.66 To a ground rod — 250.66(A) EGC — Table 250.122 Grounded conductor floor
Service — 2 AWG copper 8 AWG copper8 AWG copper6 AWG copper8 AWG copper
Service — 1/0 aluminum 8 AWG copper8 AWG copper6 AWG copper8 AWG copper
Feeder — 1 AWG copper 6 AWG copper6 AWG copper6 AWG copper6 AWG copper
Feeder — 2/0 aluminum 6 AWG copper6 AWG copper6 AWG copper6 AWG copper

Reading the table: the service runs 2 AWG copper or 1/0 aluminum, and both fall in the first row of Table 250.66, which calls for 8 AWG. The feeder runs 1 AWG copper or 2/0 aluminum, and both fall in the second row, which calls for 6 AWG. The equipment grounding conductor is 6 AWG in all four cases.

The Equipment Grounding Conductor Can Be the Larger One

On the service case the equipment grounding conductor is 6 AWG copper while the grounding electrode conductor is 8 AWG — the equipment ground is the bigger of the two. That reads like an error and it is correct.

The two conductors are sized by different rules reading different inputs. NEC Table 250.122 reads the rating of the overcurrent device, and it has no 125 ampere row — it lists 100 amperes and then 200, so a 125 ampere device reads the 200 ampere row, two steps up. NEC Table 250.66 reads the conductor, and 2 AWG copper lands in its first row. One rule rounds up past the rating; the other reads the actual wire. They are not measuring the same thing, so there is no reason for the larger rating to produce the larger conductor.

The trap inside that is interpolation. Reading between Table 250.122's 100 ampere row at 8 AWG and its 200 ampere row at 6 AWG, and landing on 8 AWG for a 125 ampere device, is wrong. The table is read upward to the first row at or above the rating, never between rows.

The Ground Rod Run, and Where It Would Bite

Where the grounding electrode conductor's sole connection is to a rod, pipe or plate electrode, NEC 250.66(A) states it is never required to be larger than 6 AWG copper. At 125 amperes that cap changes nothing in either case: the service already calls for 8 AWG and the feeder for 6 AWG, so the ceiling sits at or above what the table asks for.

It is worth knowing the cap exists because it does real work two ratings up — at 200 amperes the table calls for 4 AWG copper and 250.66(A) pulls the run to a rod down to 6 AWG, so the two figures differ. And the cap applies to that run only: a conductor serving a rod and continuing to a metal water pipe or a concrete-encased electrode is not the sole connection to the rod.

The Grounded Conductor

The grounded conductor — the neutral — is the larger of two numbers, so it is a calculation rather than a lookup. NEC 220.61 sizes it for the maximum unbalanced load, which is the maximum net calculated load between the neutral and any one ungrounded conductor. NEC 250.24(C)(1) then sets a floor from Table 250.102(C)(1), and that floor splits by case exactly as the grounding electrode conductor does: 8 AWG copper for the service, 6 AWG for the feeder. Whichever is larger governs.

NEC 310.12(D) permits the grounded conductor to be smaller than the ungrounded conductors where 220.61 and 230.42 are satisfied, which is why a reduced neutral is normal on a service. The 240 volt loads that dominate a modern dwelling put no current on the neutral at all.

At 150 Amperes These Four Rules Agree

One rating up, the split disappears. At 150 amperes the grounding electrode conductor, the ground rod cap, the equipment grounding conductor and the grounded conductor's floor all return 6 AWG copper, because both the service and feeder conductors fall in the same row of Table 250.66. That convergence is an accident of where 150 amperes lands in four different tables rather than a principle — the 150 amp wire size page says so explicitly. 125 amperes is the rating that shows what those four rules do when they are not accidentally aligned.

Cable and Conductor Types at 125 Amps

A 125 amp circuit is wired in service-entrance cable, individual conductors in conduit, or underground cable — SEU from the meter, SER for an interior feeder, THHN in conduit, USE-2 for a lateral.

NM-B Misses by 8.75 Amperes

NM-B cable cannot serve a 125 amp service, and 125 amperes is the rating where that answer is a near miss rather than an absence. 2 AWG copper NM-B is manufactured — the cable is made in 14, 12, 10, 8, 6, 4 and 2 AWG, and 2 AWG copper is exactly the conductor a 125 amp service calls for.

What disqualifies it is NEC 334.80, which holds NM-B to the 60°C column of Table 310.16 whatever the conductor's own insulation is rated. In that column 2 AWG copper carries 95 amperes, against the 103.75 the service requires. It is 8.75 amperes short. The conductor that would clear it, 1 AWG at 110 amperes in the same column, is not manufactured as NM-B at all.

That near miss is why this rating is worth stating carefully rather than waving away. At 150 and 200 amperes NM-B is out because no cable is made that large, and a reader checking the catalogue reaches the same conclusion the code does. At 125 amperes the catalogue says yes and the code says no, and the gap is small enough to look like a rounding argument. It is not one — 95 amperes is the published figure and 103.75 is the requirement.

SER and SEU

Type SEU runs from the meter socket to the service disconnect, sized as service-entrance conductors under Article 230 at the 75°C column. Type SER is the four-conductor cable used as an interior feeder downstream of the disconnect, and 2/0 aluminum SER serves a 125 amp feeder.

SE cable used for interior wiring is not held to the 60°C column the way NM-B is: NEC 338.10(B)(4)(a) requires compliance with Part II of Article 334 excluding NEC 334.80, and the 60°C rule it does impose reaches only ungrounded conductors 10 AWG and smaller installed in thermal insulation. So SER at these sizes is a 75°C conductor, which is the difference between it and NM-B. SEU has no separate equipment grounding conductor — its concentric neutral is the grounded conductor — so it cannot serve as a four-wire feeder.

USE-2, THHN and Direct Burial

Type USE-2 is the conductor for a direct-buried service lateral, rated 90°C wet and dry and used at the 75°C termination column, with burial depth from NEC Table 300.5(A). Individual THHN conductors in conduit suit a mast, a long riser or a finished wall; in wet locations the conductor is dual-rated THHN/THWN-2 and still used at 75°C. Conduit sizing comes from the fill tables in NEC Chapter 9.

Aluminum or Copper

Aluminum is what gets installed at this size, and that is why it leads here — a market judgement rather than a code one. Service-entrance cable and underground distribution conductors are predominantly aluminum at 125 amperes, and the copper equivalent costs several times as much for no gain the installation can use. Aluminum building wire at these sizes is AA-8000 series alloy; lugs must be marked AL or AL/CU, and NEC 110.14(D) requires terminations torqued to the marked value with a calibrated tool.

What the Number on the Panel Label Means

A panelboard marked 125 amperes does not require 125 amp conductors. NEC 408.36 requires that a panelboard be protected by an overcurrent device with a rating not greater than that of the panelboard — and the constraint runs one way only. The panel may be rated above the feeder supplying it.

So a 125 amp load centre fed by a 100 amp or even a 60 amp breaker is compliant, and it is a normal thing to install: the larger panel buys breaker spaces and headroom for a bigger feeder later, at a small premium over the smaller one. Nothing in that installation carries 125 amperes, and the conductor is sized to the breaker protecting it.

This is the single most useful thing to know before sizing a conductor from a panel label, and it cuts both ways. A reader who sees 125 on the label and pulls 1 AWG copper has spent money unnecessarily if the feeder breaker is 100 amperes. A reader who sees 125 on the label, pulls conductors for the 100 amp breaker actually installed, and later swaps that breaker for a 125 has created a violation without touching a wire.

What Decides the Conductor

The rating of the overcurrent device protecting it, and nothing else on the label. A 125 ampere breaker needs the conductors on this page. A 100 ampere breaker in a 125 ampere panel needs the conductors for 100 amperes, which the 100 amp wire size page covers, and the panel's own rating simply has to be at least as large as the breaker.

Common Mistakes on 125 Amp Circuits

Using 2 AWG NM-B Because the Size Exists

2 AWG copper NM-B is manufactured and it is the right conductor size for a 125 amp service, which is exactly why this one catches people. NEC 334.80 holds the cable to the 60°C column, where 2 AWG carries 95 amperes against the 103.75 required — 8.75 amperes short. The catalogue says yes and the code says no.

Sizing a Feeder from the Panel Label

NEC 408.36 permits a 125 amp panel on a smaller feeder. The breaker protecting the panel decides the conductor; the number stamped on the enclosure only has to be at least as large as that breaker.

Using the Service Conductor on a Sub-Panel Feeder

2 AWG copper is correct for a 125 amp dwelling service and 10 amperes short as a 125 amp feeder. NEC 310.12 reaches conductors supplying a dwelling's entire load and nothing else.

Assuming the Grounding Conductor Is the Same in Both Cases

It is 8 AWG copper for the service and 6 AWG for the feeder. 125 amperes is the rating where the service and feeder conductors fall either side of a row boundary in NEC Table 250.66, so getting the case wrong gets the grounding electrode conductor wrong as well as the conductor.

Interpolating the Equipment Grounding Conductor

NEC Table 250.122 lists 100 amperes and then 200, with nothing between. A 125 ampere device reads the 200 ampere row and takes 6 AWG copper; splitting the difference to 8 AWG is a violation reached by reasonable-looking arithmetic.

Expecting 240.4(D) to Apply

It caps the overcurrent device on 14, 12 and 10 AWG only. At 125 amperes there is no small-conductor limit to reconcile against the ampacity table — and the same is true of every rating on this site from 40 amperes up. The provision reaches the conductor answer at only three ratings: 15, 20 and 30 amperes, where the answer is 14, 12 and 10 AWG copper respectively.

Frequently Asked Questions

The questions this page's search data carries, answered in one sentence each before any qualification. Three are editorial additions, marked in place.

What size wire for a 125 amp service?

A 125 amp dwelling service takes 2 AWG copper or 1/0 aluminum. NEC 310.12 permits service conductors supplying a dwelling's entire load to be sized at 83 percent of the rating, which is 103.75 amperes, and those two conductors carry 115 and 120 amperes at 75°C. A 125 amp feeder to a sub-panel does not qualify and needs 1 AWG copper or 2/0 aluminum.

What size wire for a 125 amp sub panel?

1 AWG copper or 2/0 aluminum, sized against the full 125 amperes from NEC Table 310.16. A sub-panel feeder carries part of a dwelling's load, so NEC 310.12's 83 percent allowance does not reach it. That is one size larger than the service answer in each metal — and at 125 amperes it also changes the grounding electrode conductor, which it does not at 150 or 200 amperes.

What size aluminum wire for a 125 amp service?

1/0 aluminum, for a dwelling service. It is rated 120 amperes at 75°C, which clears the 103.75 amperes NEC 310.12 requires at 83 percent of a 125 amp rating. A 125 amp sub-panel feeder in aluminum needs 2/0, one size larger.

What size copper wire for a 125 amp circuit?

2 AWG copper for a dwelling service and 1 AWG copper for a sub-panel feeder. 2 AWG is rated 115 amperes at 75°C against the 103.75 amperes the 83 percent allowance requires; 1 AWG is rated 130 amperes against the full 125. Copper is uncommon at this size because the aluminum equivalent costs far less.

What size ground wire for a 125 amp service?

8 AWG copper for a dwelling service, and 6 AWG copper for a sub-panel feeder. NEC Table 250.66 reads from the size of the service conductor rather than from the rating, and at 125 amperes the two cases land in different rows of that table. The equipment grounding conductor is 6 AWG copper either way, from Table 250.122.

Why is the ground wire different for a 125 amp service and a 125 amp feeder?

Because NEC Table 250.66 is read from the conductor size, not the amperage, and the two cases use different conductors. A service runs 2 AWG copper, which falls in the table's first row for an 8 AWG grounding electrode conductor; a feeder runs 1 AWG, which falls in the second row for 6 AWG. Editorial addition — no keyword in this page's data asks this.

What size neutral wire for a 125 amp service?

Not less than 8 AWG copper for a service, or 6 AWG for a sub-panel feeder, and often larger. NEC 220.61 sizes the neutral for the maximum unbalanced load and NEC 250.24(C)(1) sets a floor from Table 250.102(C)(1); the larger governs. NEC 310.12(D) permits it smaller than the ungrounded conductors.

Can you use NM-B cable for a 125 amp service?

No, and the reason is a near miss rather than a missing size. 2 AWG copper NM-B is manufactured, but NEC 334.80 holds the cable to the 60°C column, where 2 AWG carries 95 amperes — 8.75 amperes short of the 103.75 a 125 amp service requires. The size that would clear it, 1 AWG, is not made as NM-B. Editorial addition — included because the cable looks permissible.

Does a 125 amp panel need 125 amp wire?

No. NEC 408.36 requires only that the overcurrent device protecting a panelboard not exceed the panelboard's rating, so a 125 amp panel may be fed by a smaller feeder. The conductor is sized to the breaker protecting it, not to the number on the panel label. Editorial addition — this question is not in the keyword data.

How far can you run 125 amp wire?

About 216 to 239 feet at 240 volts before voltage drop passes 3 percent, depending on the conductor: 216 feet for 1/0 aluminum, 231 feet for 2 AWG copper, 239 feet for 1 AWG copper. Those are performance targets from an informational note rather than code limits, and ampacity does not change with length.

Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions; the 83 percent dwelling service allowance is NEC 310.12, and grounding conductors are from NEC Table 250.66, Table 250.122 and Table 250.102(C)(1). Voltage drop figures are computed from NEC Chapter 9 Table 9, and the 3 percent figure is from NEC 210.19(A), Informational Note No. 4, which NEC 90.5(C) makes informational rather than enforceable. These figures are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.

Last updated: .