A 70 amp breaker needs 4 AWG copper, or 2 AWG aluminum in practice.

That is the answer that works in every wiring method, and at 70 amperes the method matters more than it does at any other rating on this site. 6 AWG copper can also take a 70 amp breaker — but only in conduit. Run the identical conductor in NM-B cable and the largest breaker it may have is 60 amperes. The difference is not the wire; it is what the wire is run in, and the rule that creates the gap is NEC 240.4(B) rather than anything in the ampacity table. There is a load limit attached to it as well. This page works that case through with all three conditions the code sets, gives the grounding conductor, and explains why 4 AWG copper in cable qualifies with no margin at all. For how conductor sizing works as a subject, see wire sizes explained.

Check the Drop on Your Own 70 Amp Run

What This Calculator Is Set To

A 70 amp circuit in 4 AWG copper at 240 volts, 100 feet one way — at the site's standard 75°C terminations. Set your own distance and read the percentage.

Solve for

You know your wire size. Find out how much voltage you'll lose.

Conductor material
Circuit type

Advanced options
Calculation method
Installation type
About installation type

Steel conduit increases voltage drop on AC circuits. If you're not sure, leave this on PVC.

Conductor temperature
About conductor temperature

The insulation's temperature rating, printed on the wire. 75°C covers most installations.

About dwelling services and main feeders

The whole electrical supply to a house or apartment, sized 100–400 amps. Not a sub-panel. Lets the conductor be sized to 83% of the rating, as the NEC allows for this case only — assuming no derating for ambient temperature or conductor count, which this calculator does not check.

About parallel sets per phase

Only if you're running more than one conductor per phase. Most circuits use 1.

About power factor

How much of the current does useful work. Motors are around 0.8, resistive loads are 1.0. Leave at 0.9 if unsure.

0.1 – 1.0

Percentage drop

1.7%

Voltage drop

4.20 V

Voltage at the load

235.80 V

R used, Ω/1000 ft

0.310

X used, Ω/1000 ft

0.0480

Under 3% Fine for a branch circuit — no action needed

How this was calculated
  1. Source: NEC Chapter 9, Table 9 — AC resistance and reactance, 75 °C
  2. R at 75 °C = 0.310 Ω/1000 ft (4 AWG copper, PVC conduit or direct burial)
  3. X = 0.0480 Ω/1000 ft (PVC conduit or direct burial)
  4. Power factor 0.90: cos θ = 0.900, sin θ = 0.436
  5. Z = R·cos θ + X·sin θ = 0.310 × 0.900 + 0.0480 × 0.436 = 0.300 Ω/1000 ft
  6. Z is computed from R and X by Table 9 note 2 at the power factor above, not read from the table’s effective-Z columns, which hold only at 0.85.
  7. Vd = 2 × I × L × Z ÷ 1000 ÷ sets
  8. Vd = 2 × 70 A × 100 ft × 0.300 ÷ 1000 ÷ 1 = 4.20 V
  9. Drop = 4.20 V ÷ 240 V × 100 = 1.7%
  10. Voltage at the load = 240 − 4.20 = 235.80 V

What Size Wire for a 70 Amp Breaker?

A 70 amp breaker takes 4 AWG copper. NEC Table 310.16 rates 4 AWG copper at 70 amperes in the 60°C column and 85 amperes at 75°C, so it carries a 70 ampere device whichever column applies to the installation — which is what makes it the answer worth memorising.

70 Amp Breaker Wire Size, by Wiring Method

In NM-B cable the answer is 4 AWG copper and nothing smaller. In conduit the answer is 4 AWG copper, or 6 AWG where the load allows it. The aluminum answer is 3 AWG by the table and 2 AWG in practice, and there is no aluminum cable case because NM-B is a copper-only product.

Why 4 AWG Sits Exactly on 70 Amperes

4 AWG copper is rated 70 amperes at 60°C — not 72, not 75. It lands precisely on the breaker rating, and that matters more here than it would at most amperages because the 60°C column is the default at this rating. NEC 110.14(C)(1)(a) limits terminations on equipment for circuits of 100 amperes or less to 60°C conductors unless the equipment is listed for more, and NEC 334.80 forces that column for NM-B regardless. So the zero-margin case is the ordinary case rather than an edge case.

A conductor sitting on its tabulated ampacity is operating as designed, not running out of room — the table's figures are the current a conductor carries continuously at its rated temperature under the conditions the table assumes. What removes the margin is conditions the table does not assume. A high ambient temperature, or more than three current-carrying conductors bundled together, requires a correction or adjustment factor under NEC 310.15, and applied to 70 amperes either one takes 4 AWG below the rating with nothing in reserve. A 70 amp cable feeder through an uninsulated attic is the case where 4 AWG stops being sufficient.

Wire Size for a 70 Amp Sub Panel

A 70 amp sub-panel feeder is 4 AWG copper or 2 AWG aluminum, with a neutral and a separate equipment grounding conductor — four conductors, with the neutral bar and ground bar isolated at the sub-panel and the main bonding jumper removed, under NEC 408.40 and 250.24(A)(5).

A 70 amp feeder commonly supplies a 100 amp sub-panel, and that is not a mismatch. NEC 408.36 requires only that the overcurrent device protecting a panelboard not exceed the panelboard's rating, so the panel may be rated above its feeder. The conductor is sized to the breaker, never to the number on the panel label. Sizing a feeder for a larger panel is covered on 125 amp wire size, where the same asymmetry is the subject.

Aluminum at 70 Amps

3 AWG aluminum is the smallest conductor the table permits, at 75 amperes in the 75°C column. 2 AWG aluminum at 90 amperes is what actually gets installed — included on market grounds rather than code grounds, because 3 AWG aluminum is barely stocked and the next size up costs little more. NEC Table 310.16 publishes no 60°C column for aluminum at all, so there is no aluminum answer to the cable question.

NEC 240.4(D) does not reach any of these sizes. That provision caps the overcurrent device on 14, 12 and 10 AWG conductors only, and the smallest conductor a 70 amp circuit uses is 4 AWG. Readers arriving from the smaller amperages expect it, because at 15, 20 and 30 amperes it is the rule that produces the answer. The rule that does the work here is a different part of the same article.

When 6 AWG Is Enough, and When It Is Not

6 AWG copper may be protected at 70 amperes in conduit, and may not in NM-B cable. The conductor is identical. What changes is the ampacity column the wiring method allows, and whether the resulting figure lands between two standard breaker ratings.

In conduit, 6 AWG copper is 65 amperes at 75°C. In NM-B, NEC 334.80 holds it to the 60°C column at 55 amperes. The standard overcurrent ratings in NEC 240.6(A) run 60, then 70, with nothing between. So the conduit figure of 65 amperes falls between two standard ratings and the cable figure of 55 amperes does not — 55 rounds up to 60, and there it stops.

The Three Conditions NEC 240.4(B) Sets

NEC 240.4(B) permits the next higher standard overcurrent rating above a conductor's ampacity, and it sets three conditions. All three must hold. The one that matters at 70 amperes is the second, but a reader who takes the rule away without the other two will apply it where it does not belong.

  • The conductors must not be part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads. A feeder to a sub-panel is not such a circuit, which is why the allowance is available here; a multi-outlet receptacle circuit would fail this condition outright.
  • The conductor's ampacity must not correspond to a standard rating. 65 amperes does not, which is the condition that does the work at 70 amperes. 55 amperes does not either — but the next standard rating above it is 60, not 70.
  • The next higher standard rating selected must not exceed 800 amperes. At 70 amperes this is never in question, and it is stated because the rule is often quoted without it.

The allowance moves one step and one step only. 6 AWG copper cannot reach an 80 amp breaker by the same route, because that would be two standard ratings up — a point the 80 amp wire size page makes from the other side.

The 65 Ampere Load Ceiling Travels With It

The permission concerns the breaker, not the load. 240.4(B) lets a 70 ampere device protect a conductor rated 65 amperes; it does not let that conductor carry 70 amperes. The load must still be within the conductor's own ampacity, so a 6 AWG copper feeder under a 70 amp breaker is limited to 65 amperes — and to 52 amperes where the load is continuous, since NEC 215.2(A)(1) requires 125 percent of a continuous load.

That is the part most easily lost. The breaker is permitted to be larger than the conductor's ampacity because it is protecting against fault and gross overload, not metering the load. If the calculated load exceeds 65 amperes, 6 AWG is the wrong conductor whatever the breaker is allowed to be.

What Installers Commonly Do

Included as practice framing rather than as a code requirement. The 6 AWG route is used — most often on a conduit or MC feeder to a sub-panel where the calculated load is comfortably under 65 amperes and the saving on a long run is worth the arithmetic. Where the run is in cable, or where the load is close to the ceiling, the common choice is simply 4 AWG, because it removes the question. Neither is more correct than the other; the second is just harder to get wrong.

70 Amp Wire Size Chart

This chart puts the two wiring methods side by side, because at 70 amperes the method decides the answer and a single ampacity column cannot express it.

Cable Against Conduit, With the Largest Breaker Each Allows

Conductors around 70 amperes: NEC Table 310.16 ampacity by column, and the largest standard breaker each wiring method permits
Conductor 60°C — NM-B cable 75°C — conduit, MC Largest breaker in cable Largest breaker in conduit
8 AWG copper 40 A50 A40 A50 A
6 AWG copper 55 A65 A60 A — not 7070 A — 240.4(B)
4 AWG copper 70 A85 A70 A — exactly90 A
2 AWG copper 95 A115 A100 A110 A
4 AWG aluminum —65 Anot a cable70 A — 240.4(B)
3 AWG aluminum —75 Anot a cable70 A
2 AWG aluminum —90 Anot a cable90 A

Reading the 6 AWG copper row: 55 amperes in cable and 65 in conduit, giving a 60 amp ceiling in cable and a 70 amp ceiling in conduit — the whole subject of this page in one row. The 4 AWG copper row is the one to use if you want a single answer: 70 amperes exactly in cable, 85 in conduit, and a 70 amp breaker either way.

The aluminum rows show a dash in the cable column because NEC Table 310.16 publishes no 60°C figures for aluminum, and because NM-B is not made with aluminum conductors. A dash there is the absence of a published value, not a zero.

Grounding a 70 Amp Circuit

The equipment grounding conductor for a 70 amp circuit is 8 AWG copper, or 6 AWG aluminum, from NEC Table 250.122 against the rating of the overcurrent device.

Equipment grounding conductor for a 70 ampere circuit, with the input each figure is read from
Circuit conductor EGC — Table 250.122 Read from
4 AWG copper 8 AWG copperthe 70 A device, rounded up to the 100 A row
3 AWG aluminum (table minimum) 8 AWG copper or 6 AWG aluminumthe 70 A device, rounded up to the 100 A row
2 AWG aluminum (what gets installed) 8 AWG copper or 6 AWG aluminumthe 70 A device — upsizing the conductor does not change it
6 AWG copper (conduit, 240.4(B)) 8 AWG copperthe 70 A device — the conductor size does not change it

The Table Has No 70 Ampere Row

NEC Table 250.122 lists 60 amperes and then 100, with nothing between, so a 70 ampere device reads the 100 ampere row — one step up from the nearest row below it. That gives 8 AWG copper rather than the 10 AWG the 60 ampere row lists.

This is where a reasonable reader goes wrong. Splitting the difference between the 60 ampere row's 10 AWG and the 100 ampere row's 8 AWG, or taking the nearer row downward, both give 10 AWG — and 10 AWG is not an acceptable equipment grounding conductor for a 70 ampere device. The table is read upward to the first row at or above the rating, never between rows and never downward.

Note also what the table reads from: the device, not the conductor. A 6 AWG copper feeder on a 70 amp breaker under 240.4(B) takes the same 8 AWG equipment grounding conductor as a 4 AWG feeder does, because the breaker has not changed. Where conductors are increased in size for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally.

Why the Service Grounding Tables Do Not Apply Here

NEC Table 250.66 sizes the grounding electrode conductor and NEC Table 250.102(C)(1) sizes the grounded conductor and the bonding jumpers. Both are service provisions, and a 70 ampere circuit is ordinarily not a service.

The reason is a floor rather than a convention: NEC 230.79(C) sets 100 amperes as the minimum service disconnect rating for a one-family dwelling, so a 70 ampere service to a house cannot exist. A 70 ampere circuit is a feeder or a branch circuit, and feeders take their equipment grounding conductor from Table 250.122 — which is the figure above. Where a 70 ampere service does exist, on a non-dwelling under NEC 230.79(D), those two tables apply and both land in their first row at 8 AWG copper. That is a different installation from the one most readers of this page have.

Cable and Conductor Types at 70 Amps

NM-B Qualifies, With No Margin

4 AWG copper NM-B serves a 70 amp circuit, and it is the only NM-B that does. NEC 334.80 holds the cable to the 60°C column where 4 AWG copper is exactly 70 amperes — it qualifies with nothing in reserve. 6 AWG is 55 amperes there, fifteen short.

Two consequences follow from that exactness. Any correction or adjustment factor under NEC 310.15 takes the conductor below its breaker, so a cable run through a hot space or bundled with others needs the next size up. And the margin is the whole reason to prefer conduit on a long or warm run, where the same conductor has fifteen amperes of headroom instead of none.

THHN in Conduit, and MC Cable

Individual THHN conductors in conduit, or Type MC cable, give the 75°C column: 4 AWG copper at 85 amperes, or 6 AWG at 65 with the conditions above. THHN is rated 90°C dry and is dual-rated THHN/THWN-2 for wet locations, but NEC 110.14(C) holds the circuit to its terminations, so 75°C is the usable figure. Conduit sizing comes from the fill tables in NEC Chapter 9.

SER, and Direct Burial

Type SER is the four-conductor cable for an interior feeder, and it is not held to the 60°C column the way NM-B is: NEC 338.10(B)(4)(a) requires compliance with Part II of Article 334 excluding NEC 334.80, and the 60°C rule it does impose reaches only ungrounded conductors 10 AWG and smaller in thermal insulation. So SER at 4 AWG is a 75°C conductor. Type UF-B is the cable for a buried 70 amp feeder, with burial depth from NEC Table 300.5(A).

Three-Phase

A 70 ampere three-phase circuit takes the same conductor. Ampacity depends on current and temperature, not on the number of phases, so 4 AWG copper carries 70 amperes per conductor either way. The breaker is three-pole and the voltage drop calculation uses a different multiplier, which the calculator above handles when the circuit type is changed.

Common Mistakes on 70 Amp Circuits

6 AWG on a 70 Amp Breaker in NM-B Cable

The commonest error at this rating, and the one that looks defensible because the same conductor is legal under the same breaker in conduit. NEC 334.80 holds the cable to 55 amperes, where the largest standard breaker is 60. In cable the answer is 4 AWG.

6 AWG in Conduit With a Load Above 65 Amperes

The 240.4(B) route is real and it carries a load ceiling. The breaker may be 70 amperes; the conductor is still a 65 ampere conductor, and 52 amperes if the load is continuous.

Treating 4 AWG's Exact 70 Amperes as Margin

In the 60°C column it is the rating, not a cushion above it. Any ambient-temperature correction or conductor-count adjustment under NEC 310.15 takes it below 70 amperes.

Reading the 75°C Column by Default

NEC 110.14(C)(1)(a) grants the 60°C column for circuits of 100 amperes or less unless the equipment is listed for higher. The 75°C figures are available in conduit with listed terminations, and they are not the starting assumption.

Interpolating the Grounding Conductor

NEC Table 250.122 lists 60 amperes and then 100. A 70 ampere device reads the 100 ampere row and takes 8 AWG copper; splitting the difference to 10 AWG is a violation reached by reasonable-looking arithmetic.

Expecting the 83 Percent Allowance

NEC 310.12 reaches services and feeders rated 100 through 400 amperes. At 70 amperes the conductor is sized against the full rating, and the calculator says so by name if you ask it.

Sizing From the Sub-Panel's Rating

NEC 408.36 permits a panel rated above its feeder, so a 70 amp feeder on a 100 amp sub-panel is normal. The breaker decides the conductor.

Frequently Asked Questions

The questions this page's search data carries, answered in one sentence each before any qualification. Four are editorial additions, marked in place.

What size wire for a 70 amp breaker?

4 AWG copper, or 3 AWG aluminum — 2 AWG aluminum in practice. NEC Table 310.16 rates 4 AWG copper at 70 amperes in the 60°C column and 85 at 75°C, so it carries a 70 ampere breaker in every wiring method. 6 AWG copper is permitted under a 70 ampere breaker only in conduit, and only where the load is 65 amperes or less.

What size wire for 70 amps?

4 AWG copper is the answer that works everywhere. It is rated exactly 70 amperes in the 60°C column of NEC Table 310.16, which is the column NEC 110.14(C)(1)(a) makes the default for circuits of 100 amperes or less, and the column NEC 334.80 forces for NM-B cable.

Can you use 6 AWG wire on a 70 amp breaker?

In conduit yes, in NM-B cable no. 6 AWG copper is 65 amperes at 75°C, and because 65 is not a standard overcurrent rating NEC 240.4(B) permits the next higher standard device — 70 amperes. In NM-B, NEC 334.80 holds the same conductor to 55 amperes, where the next standard rating is 60. Editorial addition — no keyword in this page's data asks this directly.

What size wire for a 70 amp sub panel?

4 AWG copper or 2 AWG aluminum, with a neutral and a separate equipment grounding conductor. A 70 ampere feeder is a common way to supply a 100 ampere sub-panel, because NEC 408.36 requires only that the breaker not exceed the panel's rating — the panel may be rated above its feeder.

What size ground wire for a 70 amp circuit?

8 AWG copper, or 6 AWG aluminum, from NEC Table 250.122 against the 70 ampere overcurrent device. The table lists 60 amperes and then 100, with nothing between, so a 70 ampere device reads the 100 ampere row. Interpolating between the two rows and fitting 10 AWG is a violation.

What size aluminum wire for 70 amps?

3 AWG aluminum is the table minimum at 75 amperes in the 75°C column, but 2 AWG at 90 amperes is what gets installed, because 3 AWG aluminum is barely stocked. NEC Table 310.16 publishes no 60°C column for aluminum, so there is no aluminum equivalent of the 4 AWG copper cable answer.

Does the 83 percent allowance apply to a 70 amp circuit?

No. NEC 310.12 reaches services and feeders rated 100 through 400 amperes, so a 70 ampere circuit is sized against the full 70 amperes from Table 310.16. The calculator's dwelling-service control says so by name if you tick it at this amperage rather than silently doing nothing. Editorial addition — included because readers arrive here from the larger pages.

Can NM-B cable be used for a 70 amp circuit?

Yes, in 4 AWG, and with no margin at all. NEC 334.80 holds NM-B to the 60°C column where 4 AWG copper is exactly 70 amperes — it qualifies, with nothing in reserve. 6 AWG is 15 amperes short there. Any ambient or conductor-count correction under NEC 310.15 takes 4 AWG below the rating. Editorial addition — this question is not in the keyword data.

What size wire for a 70 amp three-phase circuit?

The same conductor: ampacity depends on current and temperature, not on the number of phases. 4 AWG copper carries 70 amperes per conductor whether the circuit is single-phase or three-phase. What changes is the breaker, which is three-pole, and the voltage drop calculation, which uses a different multiplier.

Is 70 amps enough for a sub panel?

It depends on the calculated load for what the sub-panel serves, not on the panel's own rating. A 70 ampere feeder carries 70 amperes intermittently and 56 continuously, since NEC 215.2(A)(1) requires 125 percent of a continuous load. Electric heat is the load that most often exhausts it. Editorial addition — this question is not in the keyword data.

Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions; the standard overcurrent ratings are NEC 240.6(A), the next-size-up allowance is NEC 240.4(B), and the equipment grounding conductor is from NEC Table 250.122. Voltage drop figures are computed from NEC Chapter 9 Table 9. These figures are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.

Last updated: .