30 Amp Wire Size
The conductor a 30 amp breaker needs in copper and aluminum, the two voltages a 30 amp circuit runs at, and how far you can run it.
- 10 AWG copper conductor
- 10 AWG ground wire
- NFPA 70-2023 edition
A 30 amp circuit needs 10 AWG copper wire. In aluminum it needs 8 AWG rather than 10 — not as a preference but as a rule, because 10 AWG aluminum is rated exactly 30 amps and still may not be put on a 30 amp breaker.
30 amps is where a conductor's ampacity and its permitted breaker size stop being the same number. NEC Table 310.16 rates 10 AWG copper at 35 amps on 75°C terminations and 40 amps at 90°C; NEC 240.4(D)(7) holds the overcurrent device protecting it to 30 amps. Both are true at once, which is why 10 AWG and a 30 amp breaker are a matched pair — and why a 35 or 40 amp breaker on that same wire is not permitted despite the ampacity figure.
This page covers the 30 amp wire size in both materials, the two voltages a 30 amp circuit runs at, what runs on one, which cables work and how far you can run it. For conductor sizing as a subject, see wire sizes explained.
Check the Drop on Your Own 30 Amp Run
10 AWG copper is the ampacity answer at any distance, because ampacity does not change with length. What changes with length is voltage drop, so the run length is the figure left to set.
What This Calculator Is Set To
30 amps, 240 volts, copper, 10 AWG, and the site's standard 75°C terminations. If you are wiring a 30 amp RV connection, change System Voltage to 120 V — a TT-30 is a 120 volt circuit, and your voltage drop will be roughly double what this shows. Switch the mode to Find wire size and it returns 10 AWG, naming Table 310.16 as the constraint that decided it — not 240.4(D)(7), because that provision caps the breaker protecting the conductor rather than choosing the conductor itself.
What Size Wire for a 30 Amp Breaker?
The wire size for a 30 amp breaker is 10 AWG copper, or 8 AWG aluminum. That answer holds for a branch circuit at 120 volts and at 240 volts, in conduit or in cable, because ampacity is a property of the conductor and its terminations rather than of the system voltage.
30 Amp Breaker Wire Size in Copper
10 AWG copper is rated 35 amps in the 75°C column of NEC Table 310.16, which is the column that applies to almost every residential circuit because breakers and receptacles are listed for 75°C terminations under NEC 110.14(C). Against a 30 amp breaker that leaves five amps of headroom, or about 17 percent — enough that a moderately warm ambient or a modest bundle does not put the circuit in question.
The figure that decides the circuit, though, is not 35 amps. It is the 30 amps that NEC 240.4(D)(7) permits as the maximum overcurrent device on 10 AWG copper. A 30 amp breaker is therefore the largest device this conductor may take, which is what makes the pairing exact rather than merely adequate.
30 Amp Wire Size in Aluminum
In aluminum a 30 amp circuit takes 8 AWG, and the reason is the small-conductor rule rather than ampacity. 10 AWG aluminum is rated exactly 30 amps in the 75°C column, so an ampacity lookup on its own says it qualifies — and it is wrong, because NEC 240.4(D)(6) caps the overcurrent device on 10 AWG aluminum at 25 amps. There is no 30 amp breaker that may protect it.
8 AWG aluminum is rated 40 amps at 75°C and carries no small-conductor cap, so it takes a 30 amp breaker with a ten amp margin. Aluminum is genuinely usable at this size, unlike at 40 amps where 8 AWG aluminum lands exactly on the breaker rating with nothing spare.
Why 10 AWG and Not 8 AWG
8 AWG copper is not wrong for a 30 amp circuit, it is simply larger than the circuit requires — 50 amps of ampacity against a 30 amp breaker. Nothing in the code prohibits it, and on a long run it becomes the right answer for voltage drop rather than for ampacity. The question worth answering is the other direction: why 12 AWG is not permitted, since 12 AWG copper reaches 30 amps in the 90°C column and a 30 amp breaker looks like a match.
It is not a match, and the reason is the same provision read one row up. NEC 240.4(D)(5) caps the overcurrent device on 12 AWG copper at 20 amps regardless of which temperature column its insulation earns. A 30 amp breaker on 12 AWG copper is a violation whether the wire is THHN, NM-B or anything else, because the cap is written against the conductor size and not against its rating. 12 AWG copper is the conductor for a 20 amp circuit, and the 20 amp wire size page covers what that cap permits rather than what it forbids.
30 Amp Wire Size Chart
The conductor sizes either side of the answer, with the maximum breaker each one may take beside its ampacity columns:
| Conductor | 60°C column | 75°C column | 90°C column | Max breaker | Enough for 30 A? |
|---|---|---|---|---|---|
| 12 AWG copper | 20 A | 25 A | 30 A | 20 A | No — 240.4(D)(5) holds the breaker to 20 A |
| 10 AWG copper | 30 A | 35 A | 40 A | 30 A | Yes — the standard answer |
| 8 AWG copper | 40 A | 50 A | 55 A | no cap | Yes, with room to spare |
| 10 AWG aluminum | — | 30 A | 35 A | 25 A | No — 240.4(D)(6) holds the breaker to 25 A |
| 8 AWG aluminum | — | 40 A | 45 A | no cap | Yes — the aluminum answer |
In short: 10 AWG copper carries 35 amps at 75°C and takes a 30 amp breaker, which is the standard answer; 8 AWG aluminum is the aluminum answer at 40 amps of ampacity; 10 AWG aluminum and 12 AWG copper are both ruled out by their maximum breaker rather than by their ampacity, which is why an ampacity-only chart gets them wrong. For the full range of sizes and every temperature column, see the NEC ampacity table.
Why the Max Breaker Column Matters Here
On three of the five rows above, the largest permitted breaker is smaller than the conductor's 75°C ampacity. That is unusual, and it is specific to this end of the table: NEC 240.4(D) reaches only 14, 12 and 10 AWG, so 30 amps is the last amperage at which the small-conductor cap is doing the deciding. From 8 AWG upward the ampacity figure is the figure, and every larger amp page reads its answer straight from the temperature columns.
What This Table Assumes
Table 310.16 figures describe not more than three current-carrying conductors in a raceway, cable or earth, at an ambient of 30°C (86°F). Where those conditions do not hold the ampacity is reduced before it is compared against the breaker, using the ambient correction factors of Table 310.15(B)(1) and then the adjustment factors of Table 310.15(C)(1) for four or more current-carrying conductors. 240.4(D) is explicit that its caps apply after that arithmetic, not before it — the provision opens by limiting the device to its stated value "after any correction factors for ambient temperature and number of conductors have been applied."
Why Other Sites Give a Different 30 Amp Wire Size
Search for a 30 amps wire size and the answers range from 10 AWG to 8 AWG, with ampacity figures of 30, 35 and 40 amps all attached to the same conductor. Every one of those numbers is real; they come from different columns of the same table, and knowing which column a source used is what lets you reconcile them.
The Three Numbers for One Conductor
10 AWG copper is 30 amps, 35 amps or 40 amps depending on the insulation temperature rating being quoted — 60°C, 75°C or 90°C. A source quoting 40 amps is reading the 90°C column and is not wrong about the conductor, but it is describing a rating no residential circuit can use, because 110.14(C) holds the circuit to the lowest-rated termination in it and breakers are listed for 75°C. A source quoting 30 amps is reading the 60°C column, which is the one that applies inside NM-B cable. This page quotes 35 amps as the working figure and 30 amps as the permitted breaker, and states which column each came from.
Where a Different Answer Is Actually an Error
Two differences are not a matter of assumptions. A source that puts a 35 or 40 amp breaker on 10 AWG copper has missed 240.4(D)(7), and that is a safety error rather than a difference of column. A source that recommends 8 AWG for every 30 amp circuit is usually over-correcting for NM-B's 60°C limit, which as the cable section below shows does not actually bite at 30 amps. Edition matters too: this page follows NFPA 70-2023, and several of the sections it cites were renumbered in the 2020 edition.
What Voltage Is a 30 Amp Circuit?
A 30 amp circuit is 240 volts on a two-pole breaker, or 120 volts on a single-pole breaker, and both are common. 30 amps is the first amperage where that is true — at 40 and 50 amps the residential answer is always 240 volts — which makes telling the two cases apart the most useful thing this page can do. The conductor is 10 AWG copper either way; the breaker, the conductor count and the voltage drop all differ.
Wire Size for a 30 Amp 240 Volt Circuit
A 30 amp 240 volt circuit takes 10 AWG copper as two ungrounded conductors on a two-pole breaker. This is the ordinary case: an electric clothes dryer, a storage water heater, a small condenser. Both legs carry the full 30 amps, the breaker opens both together, and the conductor size comes from the same Table 310.16 row as any other 30 amp circuit.
220V, 230V or 240V?
220 volts, 230 volts and 240 volts all describe the same residential circuit, and the wire size is identical for all three. The nominal figure for a modern North American two-pole circuit is 240 volts; 220 and 230 are older nominal values that stayed in everyday speech and on appliance labels long after the distribution standard settled. If an appliance is marked 220 V or 230 V and the panel supplies 240 V, nothing about the conductor changes. Voltage drop calculations should use the actual system voltage, since the percentage is measured against it.
When a 30 Amp Circuit Is 120 Volts
A 30 amp circuit is 120 volts when it feeds a NEMA TT-30 receptacle, the 30 amp connection used for travel trailers and recreational vehicles. A TT-30 is a 125 volt, 30 amp device: one ungrounded conductor, one neutral and one equipment grounding conductor, fed by a single-pole breaker. It is the one 120 volt case in the amp tier that carries real search volume, and it is the source of the most damaging mistake on this page.
The confusion is structural rather than careless. A TT-30 has three prongs and closely resembles the legacy NEMA 10-30 dryer receptacle, which is a 125/250 volt device carrying two hots and a neutral with no equipment ground at all. Same amperage, same three prongs, and the conductor roles are inverted. An electrician who has wired hundreds of dryer outlets and never seen an RV pedestal can reasonably read a TT-30 as the receptacle it looks like.
Three-Wire or Four-Wire?
A 30 amp circuit needs four conductors when the appliance uses both 240 volts and 120 volts internally, and three when it does not. An electric dryer is the four-conductor case: the heating element runs at 240 volts while the motor, timer and controls run at 120, so it needs two hots, a neutral and an equipment grounding conductor — 10/3 with ground in cable terms. A storage water heater is the three-conductor case, with no 120 volt load and therefore no neutral: 10/2 with ground, the white conductor re-identified as the second hot at both ends.
A 120 volt TT-30 is also three conductors, and they are not the same three: one hot, one neutral, one ground. So both a dryer circuit and an RV circuit can be described as "10 AWG", and the cable you buy for one will not wire the other. Asking for 10/2 or 10/3 by name rather than by conductor count is what avoids that.
30 Amps at 12 Volts DC
A 30 amp circuit at 12 volts DC needs a far larger conductor than the same current at 240 volts, and the reason is worth following because it is the clearest demonstration on this site of why the binding constraint matters. The ampacity requirement has not changed: 30 amps still calls for 10 AWG copper, and that floor is still enforced. It simply never comes close to deciding the answer.
A 3 percent voltage drop budget is 7.2 volts at 240 volts and 0.36 volts at 12 volts. The same percentage against a twentieth of the voltage is a twentieth of the allowance, so voltage drop runs out almost immediately. Carrying 30 amps at 12 volts, 10 AWG copper reaches 3 percent at under five feet. At ten feet the answer is 6 AWG; at twenty feet it is 3 AWG, roughly five times the copper area that ampacity alone would have specified; at thirty feet it is 2 AWG.
Set against the 240 volt case, the contrast is the whole point. At 240 volts and 100 feet, ampacity and voltage drop both land on 10 AWG and neither is doing more work than the other. At 12 volts and 20 feet, voltage drop alone decides, by four conductor sizes, with the ampacity floor sitting unused far below. Same current, same code, same tool — and the answer arrives from the opposite direction. This is why a result that names only a wire size is less useful than one that says which constraint produced it.
What Runs on a 30 Amp Circuit?
A 30 amp circuit runs an RV connection, an electric clothes dryer, a storage water heater, a small air conditioner or a generator inlet. Every one of those takes 10 AWG copper and they do not all take the same cable, the same breaker or the same voltage, so the application decides more than the conductor does.
RV and Camper Connections
A 30 amp RV connection is a 120 volt circuit on 10 AWG copper with a single-pole breaker, terminating in a NEMA TT-30 receptacle. In an RV park this is the standard site supply: NEC 551.71 requires a minimum of 70 percent of recreational vehicle sites with electrical supply to be equipped with a 30 ampere, 125 volt weather-resistant receptacle conforming to the configuration in Figure 551.46(C)(1). The code writes it as 125 volts, which is the receptacle's rating; the system supplying it is nominally 120.
For a home installation the conductor is where people go wrong, and not in the direction they expect. 10 AWG copper is correct on ampacity at any length, but at 120 volts it runs out of voltage-drop headroom at 54 feet carrying the full 30 amps — against 109 feet for the same conductor and load at 240 volts. An RV pad at the end of a driveway is routinely further than that. A 100 foot run to a pedestal on 10 AWG drops 5.51 percent, which is why that installation wants 6 AWG copper even though every ampacity chart stops at 10 AWG.
The pedestal itself, the generator inlet box and a cord run from a house circuit are the same circuit with different terminations, and the single-pole requirement follows all of them. A 30 amp RV cord plugged into an adapter on a 240 volt receptacle is the failure described above, and no adapter makes it safe.
Electric Clothes Dryers
An electric clothes dryer is a 240 volt 30 amp circuit on 10 AWG copper, four conductors, terminating in a NEMA 14-30 receptacle. NEC 220.54 sets the calculated load for a household dryer at 5,000 volt-amperes or the nameplate rating, whichever is larger, which is 20.8 amps at 240 volts — comfortably inside a 30 amp circuit, and a dryer is not a continuous load.
30 amps is the amperage at which the three-wire question actually bites. NEC 250.140 requires the frame of a clothes dryer to be connected to an equipment grounding conductor, which means a new circuit is four-wire. 250.140(B) permits an existing installation to keep connecting the frame to the grounded conductor where no equipment ground is present in the box, subject to conditions — and one of those conditions is that the grounded conductor be not smaller than 10 AWG copper or 8 AWG aluminum.
That floor is the same size this page's answer produces, which is not a coincidence worth passing over. A 30 amp dryer circuit is the smallest circuit the three-wire allowance reaches, so at this amperage the allowance and the conductor answer are one number. Replacing a dryer on an existing 10-30 receptacle is permitted; running a new circuit to one is not.
Electric Water Heaters
A residential storage water heater is the cleanest 240 volt 30 amp circuit there is: 10 AWG copper, two conductors and a ground, no neutral. NEC 422.13 requires the branch circuit supplying a fixed storage-type water heater of 120 gallons or less to be rated not less than 125 percent of the nameplate rating, which treats it as a continuous load. A 4,500 watt element at 240 volts draws 18.75 amps, and 125 percent of that is 23.4 amps — so the circuit rounds up to a 30 amp breaker on 10 AWG, and the 4,500 watt heater and the 30 amp circuit became a standard pairing for that reason.
Air Conditioners and Heat Pumps
Air conditioning is the one application where 30 amps does not mean 10 AWG, and it is the clearest illustration of how the rest of this page works. Under NEC 440.4(B) the equipment nameplate carries two figures: a minimum circuit ampacity, which the conductor is sized to, and a maximum overcurrent protective device, which limits the breaker. The conductor answers to MCA, not to the breaker.
A small condenser with an MCA of 18.7 amps and an MOCP of 30 amps legally takes a 30 amp breaker on a 12 AWG copper conductor. 12 AWG is rated 25 amps at 75°C, which covers the 18.7 amp MCA, and the 30 amp device is permitted because Table 240.4(G) routes air-conditioning and refrigeration circuit conductors to Article 440 — and 240.4(D) applies only "unless specifically permitted in 240.4(E) or (G)".
The pairing is worth stating plainly, because it is the same rule twice. 240.4(D)(5) is what makes 12 AWG on a 30 amp breaker a violation everywhere else on this page, and 240.4(G) is the one place that cap is lifted. The conductor that would be an error on a dryer circuit is exactly what the manufacturer specified here.
That exception is anchored to the nameplate and it is not general permission. 12 AWG remains a violation on a 30 amp dryer, water heater, RV or generator circuit. The only thing that authorises it is an MCA and MOCP printed on a specific piece of equipment, and a conductor sized to an MCA is sized to that unit alone.
Generator Inlet Boxes
A 30 amp generator inlet box is usually a 240 volt four-wire circuit, which inverts the RV case sitting two sections above it. The common configuration is a NEMA L14-30, a 125/250 volt locking device with two hots, a neutral and a ground, wired with 10 AWG copper to a two-pole breaker through a transfer switch or interlock. Some portable-generator inlets are TT-30 instead, at 120 volts and single-pole.
So an RV pedestal and a generator inlet on the same property, both marked 30 amps, both on 10 AWG copper, can be a single-pole 120 volt circuit and a two-pole 240 volt circuit respectively. The receptacle configuration is what tells them apart, and it is worth reading the letters rather than counting the prongs.
A "30 Amp Service" Is Usually Not a Service
A 30 amp service is not permitted for a house, and most people searching for one do not have a service at all. NEC 230.79 sets minimum ratings for the service disconnecting means: 15 amperes where the service supplies one branch circuit, 30 amperes for a two-branch-circuit installation, 60 amperes for most other installations, and 100 amperes for a one-family dwelling. A 30 amp service is legal only for that narrow two-branch-circuit case.
What the search usually describes is a 30 amp feeder — to a shed, a detached garage, a small sub-panel or an RV pedestal — and a feeder is a different calculation from a service. The conductor is still 10 AWG copper on ampacity, the equipment grounding conductor still comes from Table 250.122, and the length is usually long enough that voltage drop, not ampacity, sets the size.
Where 30 Amps Is the Wrong Choice
30 amps is the wrong choice in both directions, and the over-specified direction is the one that surprises people. Too small: a household range of 8¾ kW or more may not be put on a 30 amp circuit at all, because NEC 210.19(C) sets 40 amperes as the minimum branch circuit rating for one. A house service, as above, may not be 30 amps either.
Too large is the more common error. A 30 amp branch circuit cannot be used for ordinary receptacles: Table 210.21(B)(3) requires a receptacle on a 30 amp circuit to be rated 30 amps, so standard 15 and 20 amp receptacles may not be installed on one. In a dwelling, NEC 210.23(B) restricts a 30 amp circuit to fixed utilization equipment. Anyone who ran 10 AWG and fitted a 30 amp breaker "for headroom" on a general-purpose circuit has built something that is not compliant, and the intuition that a larger breaker is safer is backwards — the breaker protects the wire, so a larger one protects it less.
One figure ties that together. 210.23(B) limits any single cord-and-plug-connected item on a 30 amp circuit to 80 percent of the circuit rating, and Table 210.21(B)(2) gives the same 24 amp maximum load directly. Read from the other end, NEC 625.41 requires an EV charging circuit to be rated 125 percent of the equipment, so a 24 amp charger is exactly a 30 amp circuit. Three separate provisions arrive at 24 amps on a 30 amp circuit — which also means a 30 amp circuit is a legitimate, if modest, Level 2 charging circuit at about 5.8 kW rather than an unsuitable one.
Electric Tankless Water Heaters
Included on code and market grounds rather than keyword grounds — there are no tankless keywords in the 30 amp file, but it is the question a reader replacing a storage heater arrives with.
A whole-house electric tankless water heater is almost never a 30 amp circuit. A 27 kW unit is three 40 amp double-pole circuits and a 36 kW unit is four, so the reader who wants to replace a 30 amp storage heater with a tankless one is usually looking at a service upgrade rather than a circuit change. 30 amps suits a small point-of-use heater and nothing larger — which makes this the one amperage in the tier where the honest tankless answer is that the circuit is not big enough.
Cable Types for a 30 Amp Circuit
NM-B, THHN in conduit and UF-B all carry a 30 amp circuit on 10 AWG copper, and the cable type changes the margin rather than the size. That holds at 40 amps as well, and it stops at 50, where NM-B's temperature limit forces a larger conductor than conduit would need.
NM-B (Romex) at 30 Amps
10 AWG NM-B carries a 30 amp circuit, and it does so with zero margin: NEC 334.80 holds non-metallic sheathed cable to the 60°C ampacity column, where 10 AWG copper is rated exactly 30 amps. The conductors inside 10/2 and 10/3 NM-B are 90°C rated, but the assembly is not, and the assembly is what governs.
Zero margin sounds fragile and mostly is not, which is where this differs from what many sources say. 334.80 permits the 90°C rating to be used for the adjustment and correction arithmetic provided the final result does not exceed the 60°C value — so derating starts from 40 amps and is then capped at 30, rather than starting from 30. A 10 AWG NM-B circuit in a 40°C attic computes 40 × 0.91 = 36.4 amps, capped back to 30: still a 30 amp circuit. Bundled with four to six current-carrying conductors it computes 40 × 0.80 = 32 amps, capped to 30: still a 30 amp circuit.
Applying the factors to 30 amps instead of 40 gives 24.6 and 24 amps respectively, and condemns two installations that are compliant. That arithmetic is the most common error in published 30 amp guidance. The combination is where it does bite: a hot attic and a bundle together compute 40 × 0.91 × 0.80 = 29.1 amps, which falls below 30 for the first time, and a circuit facing both conditions should be designed on 8 AWG rather than argued about.
The margin worth worrying about is not temperature but length. A 60°C rating of exactly 30 amps has no room for load growth, and a run long enough to need upsizing for voltage drop resolves the derating question at the same time. For how insulation and temperature ratings interact in general, see wire sizes explained.
THHN in Conduit
10 AWG THHN in conduit is the least constrained way to run a 30 amp circuit, because individual conductors in a raceway are terminated at 75°C and rated 35 amps rather than 30. The five amps of headroom absorbs an ambient correction or a fourth current-carrying conductor without recalculation, which is why commercial and garage work in conduit rarely raises the question NM-B raises. Conduit also lets the circuit be repulled later, which matters on a feeder to an outbuilding where the load may grow.
Direct Burial and UF-B
10 AWG UF-B is the direct-burial answer for a 30 amp circuit, and it carries the same 60°C limitation as NM-B under 334.80 with the same zero margin at 30 amps. Burial depth comes from Table 300.5 and the run is usually long — a shed, a well, an RV pad — so voltage drop decides the conductor more often than ampacity does. That combination argues for conduit with THHN on anything beyond a short buried run, because a buried cable cannot be repulled when the load changes and a raceway can.
What Size Ground Wire for a 30 Amp Circuit?
10 AWG copper, or 8 AWG aluminum, from NEC Table 250.122. The equipment grounding conductor is sized against the rating of the overcurrent device rather than against the circuit conductors or the ampacity table.
Table 250.122 lists no 30 ampere row. It steps from 20 amperes straight to 60, so a 30 amp device reads the 60 ampere row, which calls for 10 AWG copper. That produces something that is true only at the smallest three ratings on this site — 15, 20 and 30 amperes: the equipment grounding conductor is the same size as the circuit conductors. The coincidence tracks the small-conductor range exactly, because Table 250.122's first rows name the very conductors NEC 240.4(D) caps. At 40, 50 and 100 amps the ground is smaller than the conductors it protects, and a reader who has internalised that from another page should not expect it here.
One rule catches people on long runs. NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally where the circuit conductors are upsized for voltage drop. Take 10 AWG to 8 AWG for a long RV feeder and the 10 AWG ground grows with it — easy to miss when the reason for the upsize had nothing to do with grounding. Cable assemblies handle this themselves; individual conductors in conduit do not.
Copper vs Aluminum for 30 Amps
At 30 amps copper is the practical choice, and for once the reason is availability rather than margin. 8 AWG aluminum is a perfectly good 30 amp conductor with ten amps of headroom, but aluminum branch-circuit cable in that size is uncommon in residential supply, and the whole point of choosing aluminum — cost per foot at large sizes — barely applies at 8 AWG. Where aluminum is used, terminations must be listed AL/CU or marked for aluminum, the connection wants an antioxidant compound, and lugs should be torqued to the value marked on the device.
How Far Can You Run 30 Amp Wire?
10 AWG copper carries 30 amps about 109 feet at 240 volts and about 54 feet at 120 volts before voltage drop passes 3 percent. The gap between those two numbers is the answer to most distance questions at this amperage: the conductor is identical and the voltage halves the reach, because a percentage budget measured against 120 volts is half the volts that the same percentage allows at 240.
| One-way run | 240 V drop | 120 V drop | Verdict at 120 V |
|---|---|---|---|
| 25 ft | 0.69% | 1.38% | Fine |
| 50 ft | 1.38% | 2.75% | Fine, just inside 3% |
| 75 ft | 2.07% | 4.13% | Over 3% — upsize to 8 AWG |
| 100 ft | 2.75% | 5.51% | Over 5% — 6 AWG |
| 125 ft | 3.44% | 6.89% | Well over — 6 AWG |
| 150 ft | 4.13% | 8.26% | Well over — 4 AWG |
In short: 10 AWG copper carrying 30 amps is comfortable to 100 feet at 240 volts and needs upsizing beyond about 50 feet at 120 volts. The 3 percent branch-circuit and 5 percent combined figures come from informational notes at NEC 210.19(A) and 215.2(A) and are recommendations rather than requirements, but they are what equipment manufacturers assume.
What Size Wire for 30 Amps at 100 Feet?
At 240 volts, 10 AWG copper — a 100 foot run carrying 30 amps drops 2.75 percent, which is inside 3 percent. At 120 volts the same run drops 5.51 percent, so a 100 foot 120 volt circuit at 30 amps wants 6 AWG copper. This is the single most-asked distance question on this amperage and it has two answers, which is why a chart that lists one number per amperage cannot answer it.
When to Upsize to 8 AWG
Upsize to 8 AWG copper beyond roughly 110 feet at 240 volts, or beyond roughly 55 feet at 120 volts. Those are the points at which voltage drop rather than ampacity begins to set the conductor, and past them 10 AWG is still legal and simply performs worse than the equipment expects. Beyond about 170 feet at 240 volts, or 85 feet at 120, the answer moves again to 6 AWG. Upsizing for voltage drop also pulls the equipment grounding conductor up with it under NEC 250.122(B). Enter your own length in the calculator above rather than reading off these thresholds, since load, temperature and raceway all move them.
Common Mistakes on 30 Amp Circuits
The mistakes that actually occur at 30 amps cluster around two things: the voltage, and the belief that an ampacity figure is a breaker rating.
The Ones That Cause Damage
Wiring a TT-30 to a two-pole breaker is first by a wide margin, because it destroys equipment immediately and the receptacle gives no warning. Reading three prongs as evidence of 240 volts is the belief underneath it. The check is the breaker: a 30 amp RV circuit is single-pole, and a circuit with two hot conductors is not a TT-30 circuit however the receptacle is shaped.
Putting a 35 or 40 amp breaker on 10 AWG copper is the other damaging one, and it is usually done deliberately by someone who has checked the 90°C column and found 40 amps there. The rating is real and the installation is still a violation, because 240.4(D)(7) limits the device rather than the conductor. Under an overload, the breaker that should have opened at 30 amps holds while the wire heats.
The Ones That Cost Money
Using 10 AWG aluminum because its 75°C ampacity reads exactly 30 amps is a rework rather than a hazard, but it fails inspection: 240.4(D)(6) caps it at 25 amps. Sizing a long 120 volt run from an ampacity chart is the same kind of error in the other direction — 10 AWG is correct to 54 feet and undersized at 100. Buying 10/2 for a dryer or 10/3 for an RV outlet wastes a cable run on the right gauge and the wrong conductor count.
Derating NM-B by multiplying 30 amps by a correction factor, rather than multiplying the 90°C 40 amps and capping the result, condemns compliant work and sends people to 8 AWG unnecessarily. And fitting 15 or 20 amp receptacles to a 30 amp circuit is the over-specification error: Table 210.21(B)(3) does not permit it, so the circuit has to be rebuilt as a 20 amp circuit or terminated in a 30 amp receptacle.
Frequently Asked Questions
The questions this page's search data actually carries, answered in one sentence each before any qualification. Two are editorial additions, marked in place.
What size wire for a 30 amp breaker?
10 AWG copper on 75°C terminations. 10 AWG copper is rated 35 amps in the 75°C column of NEC Table 310.16, and NEC 240.4(D)(7) caps the overcurrent device protecting it at 30 amps, so 10 AWG and a 30 amp breaker are a matched pair. In aluminum the answer is 8 AWG, because 240.4(D)(6) caps 10 AWG aluminum at 25 amps.
What size of wire for a 30 amp circuit?
10 AWG copper, in almost every case. That holds at 240 volts and at 120 volts, because ampacity does not change with voltage — a 30 amp circuit needs a conductor rated to carry 30 amps either way. What does change with voltage is voltage drop, and that is what decides whether a long run needs 8 AWG or larger.
Can you use 12 gauge wire for 30 amps?
No. 12 AWG copper reaches 30 amps in the 90°C column of NEC Table 310.16, but NEC 240.4(D)(5) caps the overcurrent device protecting it at 20 amps, so a 30 amp breaker on 12 AWG is a violation whatever the insulation is rated. 10 AWG copper is the smallest conductor a 30 amp breaker may protect. Editorial addition — no keyword in this page's data asks this, but it is the question the small-conductor cap raises.
What size wire for a 30 amp 240 volt circuit?
10 AWG copper, as two ungrounded conductors on a two-pole breaker. A 240 volt 30 amp circuit is the standard size for an electric clothes dryer and for a 4,500 watt storage water heater. Add a neutral only if the appliance uses 120 volts internally: a dryer does and needs 10/3 with ground, a water heater does not.
Is a 30 amp RV plug 120 or 240 volts?
120 volts. A NEMA TT-30 receptacle is a 125 volt, 30 amp device fed by a single-pole breaker, carrying one hot, one neutral and an equipment grounding conductor. It has three prongs and resembles the older NEMA 10-30 dryer receptacle, which is 240 volts, and wiring a TT-30 to a two-pole breaker puts 240 volts through an RV's 120 volt system.
What size wire for a 30 amp RV plug?
10 AWG copper for runs up to roughly 50 feet, and larger beyond that. Because a TT-30 is a 120 volt circuit, its voltage drop is double what the same conductor and the same load produce at 240 volts. 10 AWG copper carrying 30 amps stays within 3 percent to 54 feet at 120 volts, against 109 feet at 240 volts.
What size wire for 30 amps at 100 feet?
That depends on the voltage, and it is where the two answers separate. At 240 volts, 10 AWG copper carrying 30 amps over 100 feet drops 2.75 percent, which is within the 3 percent branch-circuit figure. At 120 volts the same run drops 5.51 percent, so a 100 foot circuit at 120 volts needs 6 AWG copper.
What size ground wire for a 30 amp circuit?
10 AWG copper, or 8 AWG aluminum, from NEC Table 250.122. The table lists no 30 ampere row — it steps from 20 amperes to 60 — so a 30 amp overcurrent device reads the 60 ampere row. At 30 amps the equipment grounding conductor ends up the same size as the circuit conductors, which is unusual.
What size aluminum wire for 30 amps?
8 AWG aluminum. 10 AWG aluminum is rated exactly 30 amps in the 75°C column of NEC Table 310.16, so an ampacity lookup on its own suggests it qualifies, but NEC 240.4(D)(6) caps the overcurrent device on 10 AWG aluminum at 25 amps. That makes 8 AWG the smallest aluminum conductor a 30 amp breaker may protect.
Does a 30 amp dryer circuit need 10/2 or 10/3?
10/3 with ground, for any new circuit. An electric dryer draws 240 volts for the heating element and 120 volts for the motor, timer and controls, so it needs two ungrounded conductors, a neutral and an equipment grounding conductor. An existing three-wire circuit may stay in service under NEC 250.140(B), but a new one may not be wired that way. Editorial addition — no keyword in this page's data asks this, but it is the question that decides which cable to buy.
Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions; overcurrent limits apply NEC 240.4(D) and 240.6(A), equipment grounding conductors are from NEC Table 250.122, and voltage drop figures are computed from NEC Chapter 9 Table 9. They are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.