A 150 amp dwelling service needs 2/0 aluminum or 1 AWG copper. A 150 amp feeder to a sub-panel needs 3/0 aluminum or 1/0 copper — one size larger in each metal.

Aluminum comes first because aluminum is what gets installed at this size, and it is also what readers ask about more often. Two things on this page are specific to 150 amperes and worth knowing before you buy wire. Every grounding conductor is 6 AWG copper — the grounding electrode conductor, the run to a ground rod, the equipment grounding conductor and the neutral's minimum all land on the same size, which is true at this rating and not at the ones either side. And 1/0 copper carries exactly 150 amperes, with no margin at all. For how conductor sizing works as a subject, see wire sizes explained.

Check the Drop on Your Own 150 Amp Run

What This Calculator Is Set To

A 150 amp dwelling service in 2/0 aluminum, 100 feet one way — 150 amperes, 240 volts, at the site's standard 75°C terminations. Set your own distance and read the percentage.

Solve for

You know your wire size. Find out how much voltage you'll lose.

Conductor material
Circuit type

Advanced options
Calculation method
Installation type
About installation type

Steel conduit increases voltage drop on AC circuits. If you're not sure, leave this on PVC.

Conductor temperature
About conductor temperature

The insulation's temperature rating, printed on the wire. 75°C covers most installations.

About dwelling services and main feeders

The whole electrical supply to a house or apartment, sized 100–400 amps. Not a sub-panel. Lets the conductor be sized to 83% of the rating, as the NEC allows for this case only — assuming no derating for ambient temperature or conductor count, which this calculator does not check.

About parallel sets per phase

Only if you're running more than one conductor per phase. Most circuits use 1.

About power factor

How much of the current does useful work. Motors are around 0.8, resistive loads are 1.0. Leave at 0.9 if unsure.

0.1 – 1.0

Percentage drop

2.0%

Voltage drop

4.88 V

Voltage at the load

235.12 V

R used, Ω/1000 ft

0.160

X used, Ω/1000 ft

0.0430

Under 3% Fine for a branch circuit — no action needed

How this was calculated
  1. Source: NEC Chapter 9, Table 9 — AC resistance and reactance, 75 °C
  2. R at 75 °C = 0.160 Ω/1000 ft (2/0 AWG aluminum, PVC conduit or direct burial)
  3. X = 0.0430 Ω/1000 ft (PVC conduit or direct burial)
  4. Power factor 0.90: cos θ = 0.900, sin θ = 0.436
  5. Z = R·cos θ + X·sin θ = 0.160 × 0.900 + 0.0430 × 0.436 = 0.163 Ω/1000 ft
  6. Z is computed from R and X by Table 9 note 2 at the power factor above, not read from the table’s effective-Z columns, which hold only at 0.85.
  7. Vd = 2 × I × L × Z ÷ 1000 ÷ sets
  8. Vd = 2 × 150 A × 100 ft × 0.163 ÷ 1000 ÷ 1 = 4.88 V
  9. Drop = 4.88 V ÷ 240 V × 100 = 2.0%
  10. Voltage at the load = 240 − 4.88 = 235.12 V

What Size Wire for a 150 Amp Service?

A 150 amp dwelling service takes 2/0 aluminum or 1 AWG copper. NEC 310.12 permits the service conductors supplying the entire load of a one-family dwelling, or of an individual dwelling unit, to have an ampacity of not less than 83 percent of the service rating. On a 150 amp service that is 124.5 amperes, and NEC Table 310.16 rates 2/0 aluminum at 135 amperes and 1 AWG copper at 130 amperes on 75°C terminations.

The Sub-Panel Feeder Answer Is One Size Larger

A 150 amp feeder to a sub-panel takes 3/0 aluminum or 1/0 copper, sized against the full 150 amperes from Table 310.16. The allowance turns on the words "the entire load": a feeder carrying part of a dwelling's load gets no reduction, however it is wired and whatever its rating. 3/0 aluminum is rated 155 amperes and 1/0 copper exactly 150. For the same distinction worked through at the rating above this one, see 200 amp wire size.

Why 1/0 Copper Sits Exactly on 150 Amperes

1/0 copper is rated 150 amperes at 75°C — not 152, not 155. The full-rating copper answer lands precisely on the breaker rating, with a margin of zero.

That is not a conductor running out of room. Table 310.16's ampacities are the current a conductor carries continuously at its insulation's rated temperature under the conditions the table assumes, so a conductor at its tabulated ampacity is operating exactly as designed. What removes the margin is not the number but the conditions: a high ambient temperature, or more than three current-carrying conductors in a raceway, requires a correction or adjustment factor under NEC 310.15, and applied to 150 amperes either one drops 1/0 below the rating with nothing in reserve. On a feeder running through a hot attic or a crowded raceway, 2/0 copper is the conductor that survives the arithmetic.

124.5 Amperes, and What the Calculator Does With It

150 amperes is one of two ratings this site covers where 83 percent is not a whole number. 100 becomes 83 and 200 becomes 166 — but 125 becomes 103.75 and 150 becomes 124.5. Of the two awkward ones, 150 is the one that lands on a half ampere.

The calculator sizes on 124.5 and rounds only the figure it prints, so its binding sentence reads 125 amperes while the conductor it returns is computed from 124.5. That distinction is worth stating because the half-ampere cannot change an answer: Table 310.16 publishes only whole numbers, so no ampacity can be both at least 124.5 and less than 125, and the smallest conductor clearing 124.5 is therefore the same one that clears 125 in every column and both metals. The figure to work from is 124.5.

Three-Phase Gets No Reduction

NEC 310.12 applies to single-phase dwelling services and feeders, so a 150 amp three-phase service gets no reduction and is sized against the full rating. The calculator declines the allowance by name when the circuit is set to three-phase rather than applying it silently.

How Far a 150 Amp Run Reaches

A 150 amp service in 2/0 aluminum holds 3 percent voltage drop to 179 feet one way; 1 AWG copper reaches 191 feet and 1/0 copper 199 feet. At this rating voltage drop is rarely the constraint that decides a conductor, because a service run reaching those distances is unusual.

Voltage drop on a 150 ampere run at 240 volts, single-phase
One-way run 2/0 aluminum, service 1 AWG copper, service 3/0 aluminum, feeder
50 ft 0.83%0.78%0.81%
100 ft 1.67%1.56%1.63%
150 ft 2.50%2.34%2.44%
200 ft 3.33%3.13%3.25%
300 ft 5.00%4.69%4.87%

Reading the table: every conductor stays under 2 percent to 100 feet and passes 3 percent between 150 and 200 feet. The 3 percent figure is a recommendation from the informational note to NEC 210.19(A) rather than an enforceable limit — NEC 90.5(C) makes informational notes unenforceable — so a longer run is not a violation, and ampacity, which has no distance term at all, is the requirement.

150 Amp Wire Size Chart

This chart gives every conductor near a 150 amp rating against both cases, because at this rating the case decides the answer and a single column cannot express it.

Both Code Paths Against the Ampacity

Conductors for a 150 amp service and a 150 amp sub-panel feeder, NEC Table 310.16 at 75°C
Conductor Dwelling service, 310.12 Sub-panel feeder Ampacity at 75°C
2 AWG copper No — 9.5 A shortNo115 A
1 AWG copper Yes — 310.12, 83%No — 20 A short130 A
1/0 copper Yes, with marginYes — exactly 150 A150 A
2/0 copper Yes, oversizedYes, with margin175 A
1/0 aluminum No — 4.5 A shortNo120 A
2/0 aluminum Yes — 310.12, 83%No — 15 A short135 A
3/0 aluminum Yes, oversizedYes — the standard answer155 A
4/0 aluminum Yes, oversizedYes, with margin180 A

In short: 2/0 aluminum and 1 AWG copper serve a 150 amp dwelling service under NEC 310.12's 83 percent allowance, while a 150 amp sub-panel feeder needs 3/0 aluminum or 1/0 copper against the full rating. Every ampacity shown is the 75°C value, which is the column NEC 110.14(C) requires at the termination ratings of virtually all residential equipment.

Why There Is No Maximum Breaker Column

NEC 240.4(D) does not reach these sizes. That provision caps the overcurrent device on 14, 12 and 10 AWG conductors — the smallest conductor a 150 amp circuit uses is 1 AWG copper, several sizes above where it stops. Readers arriving from smaller amperages often expect it to appear, because at 15, 20 and 30 amperes it is the rule that decides the answer. Here the ampacity table and NEC 310.12 decide it between them, and there is no separate device limit to reconcile.

Grounding a 150 Amp Service: Four Rules, One Answer

Every grounding and bonding conductor on a 150 amp service is 6 AWG copper, or 4 AWG aluminum. Four separate code rules apply, they read four different inputs, and at this rating all four return the same size.

Grounding and bonding conductors for a 150 amp service, all four rules
Service conductor GEC — Table 250.66 To a ground rod — 250.66(A) EGC — Table 250.122 Grounded conductor floor
1 AWG copper (service) 6 AWG copper6 AWG copper6 AWG copper6 AWG copper
2/0 aluminum (service) 6 AWG copper6 AWG copper6 AWG copper6 AWG copper
1/0 copper (feeder) 6 AWG copper6 AWG copper6 AWG copper6 AWG copper
3/0 aluminum (feeder) 6 AWG copper6 AWG copper6 AWG copper6 AWG copper

Reading across any row: whichever of the four conductor answers the installation uses, and whichever of the four rules you apply, the result is 6 AWG copper. In aluminum every cell is 4 AWG. That is why the table looks the way it does, and it is the useful fact about grounding at this amperage.

The Grounding Electrode Conductor, From Conductor Size

The grounding electrode conductor is 6 AWG copper or 4 AWG aluminum, from NEC Table 250.66. That table is read from the size of the largest ungrounded service-entrance conductor — or the equivalent circular-mil area where the service runs in parallel sets — and not from the service rating.

Which also answers a question a reader comparing metals will reach for: the grounding electrode conductor does not change between copper and aluminum service conductors here. 1 AWG and 1/0 copper, and 2/0 and 3/0 aluminum, all fall in the same row of Table 250.66 — the row is built to pair those sizes, because two sizes of aluminum carry what one size of copper does.

The Rod Cap That Does Not Bind Here

Where the grounding electrode conductor's sole connection is to a rod, pipe or plate electrode, NEC 250.66(A) states it is never required to be larger than 6 AWG copper or 4 AWG aluminum. At 150 amperes that cap changes nothing, because Table 250.66 already calls for 6 AWG.

That is the inverse of the rating above. At 200 amperes the table calls for 4 AWG copper and 250.66(A) pulls the run to a rod down to 6 AWG, so the cap is doing real work and the two figures differ — which is covered on 200 amp wire size. At 150 amperes the cap and the table agree, so the exception is invisible in the answer. It is still worth knowing it exists, because a conductor that serves a rod and continues to a metal water pipe or a concrete-encased electrode is not the sole connection to the rod.

The Equipment Grounding Conductor, Rounded Up Two Rows

The equipment grounding conductor is 6 AWG copper or 4 AWG aluminum, from NEC Table 250.122 against the rating of the overcurrent device — not against the conductor size, and not from the ampacity table.

Table 250.122 has no 150 ampere row. It lists 100 amperes and then jumps to 200, so a 150 ampere device reads the 200 ampere row, two steps up from the nearest row below it. This is the one place on this page where a reader can go wrong by being reasonable: interpolating between the 100 ampere row's 8 AWG and the 200 ampere row's 6 AWG gives 8 AWG, and 8 AWG is not an acceptable equipment grounding conductor for a 150 ampere device. The table is read upward to the first row at or above the rating, never between rows.

Where the ungrounded conductors are increased in size for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally, so a long feeder upsized a size carries a larger equipment grounding conductor than the table lists.

The Grounded Conductor's Floor

The grounded conductor — the neutral — is the larger of two numbers, so it is a calculation rather than a lookup. NEC 220.61 sizes it for the maximum unbalanced load, which is the maximum net calculated load between the neutral and any one ungrounded conductor. NEC 250.24(C)(1) then sets a floor from Table 250.102(C)(1), which for a 150 amp service's conductors is 6 AWG copper or 4 AWG aluminum. Whichever is larger governs.

NEC 310.12(D) permits the grounded conductor to be smaller than the ungrounded conductors where 220.61 and 230.42 are satisfied, and readers are routinely surprised by that. A service in 2/0-2/0-2/0-1/0 aluminum has a neutral below its ungrounded conductors and is correct: the 240 volt loads that dominate a modern dwelling put no current on the neutral at all, so the unbalanced load is a fraction of the service rating.

Why the Convergence Is a Coincidence of 150 Amperes

Do not carry 6 AWG to another amperage. The four rules agreeing here is an accident of where 150 amperes falls in four different tables, not a principle about grounding, and it breaks immediately at the rating above.

At 200 amperes the same four rules give 4 AWG for the grounding electrode conductor, 6 AWG for the run to a rod, 6 AWG for the equipment grounding conductor and 4 AWG for the grounded conductor's floor — two different answers where 150 amperes gives one. Nothing about the rules changed; the service conductors moved into the next row of two of the four tables. Each rule has to be read separately at every rating, and a page that tells you all four are the same size is telling you something about 150 amperes rather than about grounding.

One rating down shows the same four rules splitting rather than agreeing. At 125 amperes the service and feeder conductors fall either side of a row boundary in Table 250.66, so a service takes an 8 AWG grounding electrode conductor and a feeder takes 6 AWG — the same rating, the same house, two answers. The 125 amp wire size page works that through, and it is the better illustration of how these rules behave when they are not accidentally aligned.

Cable and Conductor Types at 150 Amps

A 150 amp service is wired in service-entrance cable, individual conductors in conduit, or underground cable — SEU from the meter, SER for an interior feeder, THHN in conduit, and USE-2 for a lateral.

Aluminum Leads at This Size

Aluminum is included first on practical grounds as well as search grounds. Service-entrance cable and underground distribution conductors are predominantly aluminum at this rating, and the copper equivalent costs several times as much for no gain the installation can use. Unlike some larger ratings, the search data agrees: aluminum phrasings outnumber copper ones on this page's keyword file by about three to two, and the single easiest term on the file asks for the aluminum size.

Aluminum building wire at these sizes is AA-8000 series alloy, which is what makes it suitable for the terminations it lands on. Lugs must be marked AL or AL/CU, and NEC 110.14(D) requires terminations to be torqued to the marked value with a calibrated tool. The 200 amp wire size page covers aluminum terminations in more detail; nothing about them is specific to 150 amperes.

SER and SEU

Type SEU runs from the meter socket to the service disconnect and is sized as service-entrance conductors under Article 230 at the 75°C column. Type SER is the four-conductor cable used as an interior feeder downstream of the disconnect, and 2/0 aluminum SER serves a 150 amp dwelling service.

SE cable used for interior wiring is not held to the 60°C column: NEC 338.10(B)(4)(a) requires compliance with Part II of Article 334 excluding NEC 334.80, and the 60°C ampacity rule it does impose reaches only ungrounded conductors 10 AWG and smaller installed in thermal insulation. Every conductor on this page is far above that. SEU has no separate equipment grounding conductor, so it cannot serve as a four-wire feeder however convenient its profile is.

USE-2, THHN and Direct Burial

Type USE-2 is the conductor for a direct-buried service lateral, rated 90°C wet and dry and used at the 75°C termination column, with burial depth from NEC Table 300.5(A). Individual THHN conductors in conduit are the usual choice through a mast, a long riser or a finished wall; in the wet locations a service raceway counts as, the conductor is dual-rated THHN/THWN-2 and still used at 75°C. Conduit sizing comes from the fill tables in NEC Chapter 9.

NM-B Does Not Reach 150 Amperes

NM-B is not a candidate, and not because of its temperature limitation. The cable is manufactured in 14, 12, 10, 8, 6, 4 and 2 AWG, and the smallest conductor a 150 amp service uses is 1 AWG copper. There is no 150 amp NM-B answer to evaluate.

When 150 Amps Is Not Enough

Whether 150 amperes suits a house is answered by an Article 220 load calculation and by nothing else. NEC 230.79(C) sets 100 amperes as the floor for a one-family dwelling, so 150 amperes is above the code minimum — being smaller than the usual new-build service is not by itself a reason to replace it.

What Exhausts It

A small number of large continuous loads, arriving one step sooner than they would at 200 amperes. An electric vehicle charger is calculated as a continuous load at 125 percent under NEC 625.42, so a 48 ampere charger is 60 amperes of calculated demand before anything else counts. Electric resistance heat, a heat pump with resistance backup and an induction range each add materially. For an existing dwelling adding load, NEC 220.83 is the calculation that decides it.

Where the calculation does not fit, the usual answer is a 200 ampere service — covered on 200 amp wire size, including the load-management alternative under NEC 220.70 and Article 750 that often avoids the upgrade entirely.

A Standard Rating That New Construction Stopped Choosing

Included as market context rather than as a code requirement. 150 amperes is a standard overcurrent rating under NEC 240.6(A) and panels are still made in it, but new residential construction has largely settled on 200 amperes, so a 150 amp service is encountered more often than it is specified. No code change caused that and the code has never required either figure beyond the 100 ampere minimum; it is a market pattern, and it is the reason this rating can feel undersized when the load calculation says otherwise.

Common Mistakes on 150 Amp Services

Interpolating the Grounding Conductor Between Table Rows

Table 250.122 lists 100 amperes and then 200, with nothing between. A 150 ampere device reads the 200 ampere row and takes 6 AWG copper; splitting the difference and fitting 8 AWG is a violation arrived at by reasonable-looking arithmetic.

Using the Service Conductor on a Sub-Panel Feeder

1 AWG copper is correct for a 150 amp dwelling service and 20 amperes short as a 150 amp sub-panel feeder. NEC 310.12 reaches conductors supplying a dwelling's entire load, and nothing else.

Treating 1/0 Copper's Exact 150 Amperes as Margin

It is the rating, not a cushion above it. Any correction or adjustment factor under NEC 310.15 — a hot attic, a crowded raceway — takes it below 150 amperes.

Carrying the 6 AWG Answer to Another Amperage

The four rules converging is specific to 150 amperes. At 200 amperes the grounding electrode conductor and the grounded conductor's floor are both 4 AWG while the rod run and the equipment grounding conductor stay at 6.

Reading the Service Rating off the Panel Instead of the Main Breaker

A panel's enclosure may be rated for more than the breaker installed in it. A load centre labelled 200 amperes with a 150 ampere main is a 150 ampere service, and the breaker is what the conductors answer to.

Expecting 240.4(D) to Apply

It caps the overcurrent device on 14, 12 and 10 AWG only. At 150 amperes there is no small-conductor limit to reconcile against the ampacity table — and the same is true of every rating on this site from 40 amperes up. The provision reaches the conductor answer at only three ratings: 15, 20 and 30 amperes.

Frequently Asked Questions

The questions this page's search data carries, answered in one sentence each before any qualification. Four are editorial additions, marked in place.

What size wire for a 150 amp service?

A 150 amp dwelling service takes 2/0 aluminum or 1 AWG copper. NEC 310.12 permits service conductors supplying a dwelling's entire load to be sized at 83 percent of the rating, which is 124.5 amperes, and those two conductors carry 135 and 130 amperes at 75°C. A 150 amp feeder to a sub-panel does not qualify and needs 3/0 aluminum or 1/0 copper.

What size aluminum wire for a 150 amp service?

2/0 aluminum, for a dwelling service. It is rated 135 amperes at 75°C, which clears the 124.5 amperes NEC 310.12 requires at 83 percent of a 150 amp rating. Aluminum is the usual conductor at this size. A 150 amp sub-panel feeder in aluminum needs 3/0, one size larger.

What size copper wire for a 150 amp service?

1 AWG copper, for a dwelling service, rated 130 amperes at 75°C against the 124.5 amperes NEC 310.12 requires. A 150 amp sub-panel feeder in copper needs 1/0, which Table 310.16 rates at exactly 150 amperes — no margin above the breaker rating.

Is 1/0 copper enough for a 150 amp feeder?

Yes, and with no margin. NEC Table 310.16 rates 1/0 copper at exactly 150 amperes on 75°C terminations, so it sits precisely on the breaker rating. That is a conductor operating as designed, but any ambient-temperature correction or conductor-count adjustment under NEC 310.15 drops it below 150 with nothing in reserve. Editorial addition — no keyword in this page's data asks this.

What size ground wire for a 150 amp service?

6 AWG copper, or 4 AWG aluminum — and unusually, that is the answer for every grounding conductor a 150 amp service needs. The grounding electrode conductor from NEC Table 250.66, the run to a ground rod under 250.66(A), the equipment grounding conductor from Table 250.122, and the grounded conductor's minimum from Table 250.102(C)(1) all land on 6 AWG copper at this rating.

What size neutral wire for a 150 amp service?

Not less than 6 AWG copper, and usually larger. NEC 220.61 sizes the neutral for the maximum unbalanced load and NEC 250.24(C)(1) sets a floor of 6 AWG copper from Table 250.102(C)(1); the larger of the two governs. NEC 310.12(D) permits it smaller than the ungrounded conductors, which is why a reduced neutral is normal on a service.

What size wire for a 150 amp sub panel?

3/0 aluminum or 1/0 copper. A sub-panel feeder carries part of a dwelling's load, so NEC 310.12's 83 percent allowance does not apply and the conductor is sized against the full 150 amperes from Table 310.16. That is one size larger than the service answer in each metal.

How far can you run 150 amp wire?

About 180 to 200 feet before voltage drop passes 3 percent at 240 volts, depending on the conductor: 179 feet for 2/0 aluminum, 191 feet for 1 AWG copper, 199 feet for 1/0 copper. Those are performance targets from an informational note rather than code limits. Ampacity does not change with length. Editorial addition — the distance keywords on this page carry almost no volume.

Does 240.4(D) apply at 150 amps?

No. NEC 240.4(D) limits the overcurrent device on 14, 12 and 10 AWG conductors only, and the smallest conductor a 150 amp circuit uses is 1 AWG copper. Readers arriving from smaller amperages often expect it to apply; at this size the ampacity table and NEC 310.12 decide the answer on their own. Editorial addition — included because the question is implied rather than asked.

Is a 150 amp service enough for a house?

It depends on the Article 220 load calculation and on nothing else. NEC 230.79(C) sets 100 amperes as the floor for a one-family dwelling, so 150 amperes is above the code minimum. What exhausts it is a small number of large continuous loads — an EV charger at 125 percent under NEC 625.42, electric heat, a heat pump. Editorial addition — this question is not in the keyword data.

Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions; the 83 percent dwelling service allowance is NEC 310.12, and grounding conductors are from NEC Table 250.66, Table 250.122 and Table 250.102(C)(1). Voltage drop figures are computed from NEC Chapter 9 Table 9, and the 3 percent figure is from NEC 210.19(A), Informational Note No. 4, which NEC 90.5(C) makes informational rather than enforceable. These figures are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.