A 20 amp circuit needs 12 AWG copper, or 10 AWG aluminum.

That answer does not change with voltage, with the cable type, or with whether you call it a 20 amp breaker or a 20 amp circuit — at this rating those are one question. What does change is the reasoning, and it matters more here than at any other amperage: in the temperature column the code makes the default for a circuit this size, 12 AWG copper carries exactly 20 amperes and the answer comes straight off the ampacity table. In the warmer column, 14 AWG would carry 20 amperes too, and a separate rule forbids protecting it at 20. This page gives both routes, answers the 14 AWG question that causes more wiring faults in American houses than any other, covers the 240 volt 20 amp circuit, and shows how far 12 AWG runs before voltage drop — not ampacity — becomes the limit. For how conductor sizing works as a subject, see wire sizes explained.

Check the Drop on Your Own 20 Amp Run

What This Calculator Is Set To

A 20 amp circuit at 120 volts in 12 AWG copper, 50 feet one way — a typical household run. Set your own distance and read the percentage.

Solve for

You know your wire size. Find out how much voltage you'll lose.

Conductor material
Circuit type

Advanced options
Calculation method
Installation type
About installation type

Steel conduit increases voltage drop on AC circuits. If you're not sure, leave this on PVC.

Conductor temperature
About conductor temperature

The insulation's temperature rating, printed on the wire. 75°C covers most installations.

About dwelling services and main feeders

The whole electrical supply to a house or apartment, sized 100–400 amps. Not a sub-panel. Lets the conductor be sized to 83% of the rating, as the NEC allows for this case only — assuming no derating for ambient temperature or conductor count, which this calculator does not check.

About parallel sets per phase

Only if you're running more than one conductor per phase. Most circuits use 1.

About power factor

How much of the current does useful work. Motors are around 0.8, resistive loads are 1.0. Leave at 0.9 if unsure.

0.1 – 1.0

Percentage drop

3.0%

Voltage drop

3.65 V

Voltage at the load

116.35 V

R used, Ω/1000 ft

2.000

X used, Ω/1000 ft

0.0540

3–5% Acceptable if it's the feeder portion and total stays under 5%, but check

How this was calculated
  1. Source: NEC Chapter 9, Table 9 — AC resistance and reactance, 75 °C
  2. R at 75 °C = 2.000 Ω/1000 ft (12 AWG copper, PVC conduit or direct burial)
  3. X = 0.0540 Ω/1000 ft (PVC conduit or direct burial)
  4. Power factor 0.90: cos θ = 0.900, sin θ = 0.436
  5. Z = R·cos θ + X·sin θ = 2.000 × 0.900 + 0.0540 × 0.436 = 1.824 Ω/1000 ft
  6. Z is computed from R and X by Table 9 note 2 at the power factor above, not read from the table’s effective-Z columns, which hold only at 0.85.
  7. Vd = 2 × I × L × Z ÷ 1000 ÷ sets
  8. Vd = 2 × 20 A × 50.0 ft × 1.824 ÷ 1000 ÷ 1 = 3.65 V
  9. Drop = 3.65 V ÷ 120 V × 100 = 3.0%
  10. Voltage at the load = 120 − 3.65 = 116.35 V

What Size Wire for a 20 Amp Breaker or Circuit?

A 20 amp circuit takes 12 AWG copper or 10 AWG aluminum. The conductor is sized against the rating of the overcurrent device protecting it, so a 20 amp breaker and a 20 amp circuit have the same answer — which is not true at every amperage, but is true here.

20 Amp Circuit Breaker Wire Size

12 AWG copper is the conductor for a 20 amp circuit breaker. NEC 240.4(D)(5) permits a 20 ampere overcurrent device on 12 AWG copper, and that is the largest breaker the conductor may have regardless of which ampacity column applies to the installation.

Why 12 AWG and Not 14 AWG

14 AWG copper is excluded by NEC 240.4(D)(3), which limits its overcurrent device to 15 amperes. This is the part almost every other source states too simply, and the precise version is more useful.

NEC 240.4(D) limits the overcurrent device. It does not limit ampacity and it does not override Table 310.16. 14 AWG copper genuinely carries 20 amperes at 75°C and 25 amperes at 90°C — those are its real ampacities. What it cannot have is a 20 ampere breaker. A conductor's ampacity and its permitted overcurrent device are two different numbers, and conflating them is how the 14 AWG mistake gets rationalised after the fact.

Which Temperature Column Applies, and When the Rule Actually Bites

NEC 110.14(C)(1)(a) makes the 60°C column the default for circuits rated 100 amperes or less, and for terminations marked for 14 AWG through 1 AWG conductors — unless the equipment is listed and identified for a higher temperature. Most modern devices are listed for 75°C, so both columns are in play in real installations, and the two produce the same conductor by different routes.

In the 60°C column, 12 AWG copper carries exactly 20 amperes and 14 AWG carries 15. The ampacity table alone produces 12 AWG, and neither small-conductor cap does any work — 240.4(D)(5) permits a 20 ampere breaker on a conductor that was already limited to 20 amperes by its ampacity.

In the 75°C column, 12 AWG carries 25 amperes and 14 AWG carries 20. A reader sizing on ampacity alone would stop at 14 AWG, because 20 amperes of ampacity satisfies a 20 ampere load. What forbids it is NEC 240.4(D)(3). So the rule that creates the answer is the one foreclosing 14 AWG, not the one confirming 12 — and it only has anything to do in the column where 14 AWG looks adequate.

Aluminum at 20 Amps

10 AWG aluminum is the answer, not 12 AWG, and the reason is the same rule acting one size further down: NEC 240.4(D)(4) caps 12 AWG aluminum at 15 amperes even though Table 310.16 rates it 20 amperes at 75°C. Aluminum is rare on 20 amp branch circuits — NEC 310.3(A) sets 12 AWG as the smallest aluminum conductor permitted at all, and most jurisdictions and most devices make copper the practical choice at this size.

20 Amp Wire Size Chart

This chart puts the ampacity columns beside the maximum breaker each conductor may have, because at 20 amperes the gap between those two numbers is the whole subject.

Ampacity Against Maximum Breaker

Conductors around 20 amperes: NEC Table 310.16 ampacities and the 240.4(D) overcurrent limit
Conductor 60°C — the default at 20 A 75°C 90°C Max breaker — 240.4(D)
14 AWG copper 15 A20 A25 A15 A — 240.4(D)(3)
12 AWG copper 20 A25 A30 A20 A — 240.4(D)(5)
10 AWG copper 30 A35 A40 A30 A — 240.4(D)(7)
12 AWG aluminum —20 A25 A15 A — 240.4(D)(4)
10 AWG aluminum —30 A35 A25 A — 240.4(D)(6)

Reading the 12 AWG copper row: 20 amperes at 60°C, 25 at 75°C, 30 at 90°C, and a maximum breaker of 20 amperes whichever column applies. The 14 AWG row is the one that matters — 20 amperes of ampacity at 75°C against a 15 ampere maximum breaker, which is the entire reason 14 AWG cannot serve a 20 amp circuit. Aluminum has no 60°C column in Table 310.16, which is why those cells read as a dash rather than a number.

Why the 90°C Column Is Not the Answer

12 AWG copper is rated 30 amperes at 90°C, and that figure never sizes a residential circuit. NEC 110.14(C) limits a conductor to the lowest temperature rating of any termination in the circuit, and a 20 ampere breaker, receptacle and device box are listed for 60°C or 75°C. The 90°C rating on the insulation is real, and it is used for derating calculations — correcting for ambient temperature or for several current-carrying conductors in a raceway — not for reading a conductor off the table.

Can You Use 14 AWG on a 20 Amp Breaker?

No. NEC 240.4(D)(3) limits the overcurrent device on 14 AWG copper to 15 amperes, so a 20 ampere breaker on 14 AWG is a violation whatever the conductor's ampacity is. If you have found 14 AWG on a 20 amp breaker, the breaker is the wrong component, not necessarily the wire — fitting a 15 ampere breaker makes the existing cable correct, and 15 amp wire size covers what that circuit can then carry.

What Actually Happens

The conductor is not usually the thing that fails. 14 AWG copper carries 15 to 25 amperes depending on the column, so a 14 AWG circuit drawing 18 amperes is inside its own ampacity at 75°C and the conductor runs warm rather than glowing. The hazard is that the breaker never opens. A 20 ampere device will carry 18 amperes indefinitely, so a sustained overload on a conductor and terminations rated for 15 sits there heating connections, degrading insulation at device boxes, and giving no indication at the panel. What a correctly sized breaker would have turned into a nuisance trip becomes a slow thermal problem in a wall.

Why the Mistake Is So Common

Three different routes lead here, and the remedy differs for each.

Breaker replacement is the most common. A 15 ampere breaker trips repeatedly, a 20 ampere breaker fits the same panel slot, and the tripping stops. The conductor was never touched and the protection is now wrong. The tripping was information, and replacing the breaker discarded it.

Mixed-gauge extension is the second. An existing 12 AWG 20 amp circuit is extended with 14 AWG because that is what was on the van, which leaves a 20 ampere circuit with a 14 AWG segment. The circuit is only as protected as its smallest conductor.

The third is reasoning from the wrong column, and it is the one that feels rigorous. 14 AWG copper is rated 20 amperes at 75°C and 25 at 90°C, so a reader who finds those numbers concludes 14 AWG is a 20 ampere conductor. It is — by ampacity. NEC 240.4(D)(3) is a separate limit on the device, and it does not appear in the ampacity table at all.

How to Tell What You Have

The fastest check is the cable jacket colour. Since around 2001, manufacturers of NM-B cable have followed a colour convention: 14 AWG is white, 12 AWG is yellow, and 10 AWG is orange. This is a manufacturer convention rather than a code requirement, so it is a strong indication rather than proof, and it does not apply to cable older than that or to conductors in conduit.

The authoritative marking is the legend printed along the jacket, which reads the size and conductor count directly — 12-2 WITH GROUND — and is correct regardless of colour. Where the cable is not visible, the conductor at a device can be compared against a wire gauge, with the circuit de-energised. Checking at one device is not enough if a mixed extension is possible: the undersized segment may be anywhere on the circuit.

What to Do About It

There are two compliant outcomes and the choice is about what the circuit needs to carry. Fitting a 15 ampere breaker makes the existing 14 AWG correct and reduces the circuit's capacity, which is the right answer where the circuit serves lighting or general receptacles. Pulling new 12 AWG keeps the 20 ampere capacity and is necessary where the circuit is one the code requires to be 20 amperes — a kitchen small-appliance circuit, a bathroom circuit or a laundry circuit, all covered further down this page.

What Voltage Is a 20 Amp Circuit?

Most 20 amp circuits are 120 volts, and the conductor is 12 AWG copper at either voltage. Ampacity depends on current and on temperature, not on voltage, so a 240 volt 20 amp circuit takes exactly the same conductor as a 120 volt one.

That is worth stating plainly because the search data suggests people doubt it. Readers ask about the 240 volt 20 amp circuit far more often than the 120 volt one, which is the opposite of how often each is installed — and the likeliest reason is that a 240 volt circuit feels like it should need something different.

At 120 Volts

A 120 volt 20 amp circuit is 12 AWG copper, a single-pole 20 ampere breaker, and two current-carrying conductors plus an equipment grounding conductor — 12/2 NM-B in most houses. It delivers 2,400 volt-amperes, or 1,920 for a continuous load. This is the circuit behind kitchen receptacles, bathroom receptacles, garage outlets and general-purpose receptacles in most of the house.

The 240 Volt 20 Amp Circuit

A 240 volt 20 amp circuit is 12 AWG copper on a two-pole breaker, which occupies two panel slots and opens both ungrounded conductors together. It delivers 4,800 volt-amperes, or 3,840 for a continuous load — double the 120 volt circuit on the same conductor, which is the entire reason anyone wires one.

What runs on one: electric baseboard heat is the dominant case, and at 3,840 watts of continuous capacity a 20 amp 240 volt circuit carries roughly 15 feet of 250-watt-per-foot baseboard. Small mini-split condensers and window air conditioners are the next most common, along with some well pumps and 240 volt shop tools. Baseboard heat is a genuinely continuous load, so the 80 percent limit covered further down this page applies to it directly rather than theoretically.

Two-Wire or Three-Wire?

A purely 240 volt load needs two ungrounded conductors and an equipment grounding conductor, and no neutral — 12/2 cable, with the white conductor re-identified as ungrounded where the wiring method and NEC 200.7 permit it. A load needing both 240 and 120 volts, such as some appliances with 120 volt controls, needs a neutral as well, which means 12/3 cable. Checking the equipment's nameplate before buying cable is cheaper than discovering it afterwards.

How Far Can You Run 20 Amp Wire?

12 AWG copper on a 20 amp circuit holds 3 percent voltage drop to 44 feet at 120 volts and 89 feet at 240 volts, one way. There is no code limit on the length of a branch circuit, so a longer run is not a violation — but 20 amps at 120 volts is the amperage in this tier where voltage drop, not ampacity, decides what a sensible conductor is.

The 3 Percent Figure Is Advisory, Not Mandatory

The 3 percent figure appears in NEC 210.19(A), Informational Note No. 4, which suggests that branch-circuit conductors sized to prevent a voltage drop exceeding 3 percent at the farthest outlet, with no more than 5 percent total across feeders and branch circuits, provide reasonable efficiency of operation. The parallel note for feeders is NEC 215.2(A), Informational Note No. 2.

NEC 90.5(C) states that informational notes are informational only and are not enforceable as requirements of the code. So neither figure is a limit an inspector can fail you on, and a 20 amp circuit at 5 percent drop is code-compliant. It is also delivering 114 volts to equipment designed for 120, which is why the figure exists and why it is worth designing to. Ampacity is the requirement; voltage drop is a performance target.

At 120 Volts, the Budget Is 3.6 Volts

Three percent of 120 volts is 3.6 volts, and that is a small allowance for a 20 ampere load. 12 AWG copper spends it at 44 feet and reaches 5 percent by 75 feet — distances that occur inside an ordinary house, not on a run to an outbuilding.

Voltage drop on a 20 ampere circuit, one-way run, copper
One-way run 12 AWG at 120 V 10 AWG at 120 V 12 AWG at 240 V
25 ft 1.67%1.00%0.83%
50 ft 3.33%2.00%1.67%
75 ft 5.00%3.00%2.50%
100 ft 6.67%4.00%3.33%
150 ft 10.00%6.00%5.00%
200 ft 13.33%8.00%6.67%

Reading the table: 12 AWG at 120 volts passes 3 percent between 25 and 50 feet and 5 percent between 50 and 75 feet, while the same conductor at 240 volts stays under 3 percent to nearly 100 feet. Upsizing to 10 AWG at 120 volts roughly doubles the reach, holding 3 percent to 74 feet, and 8 AWG holds it to 115 feet.

When to Upsize, and What It Costs

Upsizing is worth it on a long 120 volt run to a garage, a workshop receptacle or an outdoor circuit, and on anything driving a motor, since low voltage at starting is what shortens motor life. It is rarely worth it on a lighting circuit with LED loads, which tolerate voltage variation well, or on a short kitchen run.

Two constraints on upsizing that are easy to miss. The breaker stays at 20 amperes — upsizing the conductor does not increase the circuit's rating, because the rating is the breaker's. And where conductors are increased in size, NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally, so a circuit upsized to 10 AWG carries a 10 AWG equipment grounding conductor rather than the 12 AWG that Table 250.122 lists for a 20 ampere device.

A 20 ampere circuit at 12 volts DC is a different calculation entirely and this page does not cover it. At that voltage a 3 percent budget is 0.36 volts and the conductor is far larger than anything in the table above.

Wire Size for a 20 Amp Outlet

A 20 amp outlet takes 12 AWG copper, the same as the circuit feeding it. The conductor is sized against the breaker, not against the receptacle — which matters because the receptacle on a 20 amp circuit does not have to be a 20 ampere receptacle.

Why a 15 Amp Receptacle on a 20 Amp Circuit Is Legal

Table 210.21(B)(3) permits either a 15 ampere or a 20 ampere receptacle on a 20 ampere branch circuit serving two or more outlets. Nearly every general-purpose 20 amp circuit in a modern house is wired with 15 ampere duplex receptacles, and it is fully compliant.

This is the one thing on this page that reliably surprises people, because it runs the opposite way from everything else about circuit sizing. The conductor must be able to carry the breaker's rating. The receptacle does not. The reason is what a receptacle rating means: it is the maximum a single plugged-in load may draw through that device, and NEC 210.21(B)(2) limits a cord-and-plug-connected load on one receptacle of a multi-outlet circuit to 12 amperes — 80 percent of 15. The circuit can supply 20 amperes in total across several receptacles; no one receptacle is expected to deliver it.

Where a 20 Amp Receptacle Is Actually Required

Three situations call for the 5-20R specifically. A single receptacle on an individual 20 ampere branch circuit requires it under 210.21(B)(1), as above. Equipment supplied with a 20 ampere plug requires a matching receptacle, which is the practical reason most shop and garage circuits get them. And some jurisdictions amend the code to require 20 ampere receptacles on kitchen small-appliance circuits, which the NEC itself does not — worth checking locally rather than assuming either way.

The 20 Amp Circuits the Code Requires

Three places in a dwelling must have 20 ampere circuits by name: the kitchen, the bathroom and the laundry. All three take 12 AWG copper, and all three are among the most frequently missed requirements in renovation work.

This section is included on code grounds rather than keyword grounds. No search term in this page's data asks about kitchen, bathroom or laundry circuits — not a low number, zero — yet these are the 20 ampere circuits a homeowner is most likely to be affected by. The demand exists in questions nobody phrases as a wire-size question.

Kitchen Small-Appliance Circuits — Two Minimum

NEC 210.11(C)(1) requires a minimum of two 20 ampere small-appliance branch circuits to serve the receptacle outlets specified in 210.52(B) — the countertop, dining and breakfast-area receptacles. Two, not one. A kitchen rewired onto a single 20 ampere circuit is the most common violation found in remodels, and it fails for a reason a homeowner notices: a kettle and a toaster together will trip it.

These circuits serve receptacles, and 210.52(B)(2) restricts them from supplying other outlets, with specific exceptions for things like a clock outlet and gas-range ignition. Lighting does not go on them.

Bathroom Circuits

NEC 210.11(C)(3) requires at least one 20 ampere branch circuit to supply bathroom receptacle outlets, and that circuit must have no other outlets — with an exception permitting it to supply the rest of a single bathroom, so one circuit may serve one bathroom's receptacles, lighting and fan together. What it may not do is serve two bathrooms' receptacles and also the hallway lights.

The Laundry Circuit

NEC 210.11(C)(2) requires at least one additional 20 ampere branch circuit for the laundry receptacle outlets required by 210.52(F), and that circuit shall have no other outlets. A washing machine shares it with nothing. An electric dryer is a separate matter entirely — that is a 240 volt circuit at 30 amperes, covered on the 30 amp wire size page.

Cable Types for a 20 Amp Circuit

12/2 NM-B cable is the default wiring method for a 120 volt 20 amp circuit in a dwelling, and 12 AWG is the conductor in every other method as well.

NM-B — and Why the 60°C Limit Does Not Bite Here

NEC 334.80 holds NM-B cable to the 60°C column of Table 310.16 whatever the conductor's own insulation rating is. At 20 amperes that changes nothing: 12 AWG copper is exactly 20 amperes in the 60°C column, so 12/2 NM-B serves a 20 amp circuit, and the cable answer and the conduit answer are the same conductor.

A conductor sitting precisely on its rating sounds precarious and is not. Table 310.16's ampacities are the current a conductor carries continuously at its rated temperature under the conditions the table assumes, so a 12 AWG conductor carrying 20 amperes is operating exactly as designed with no margin consumed. What removes margin is conditions the table does not assume — a high ambient temperature, or more than three current-carrying conductors bundled together, each of which calls for a correction or adjustment factor under NEC 310.15. Applied to a conductor already at 20 amperes, either one drops it below the breaker rating. A 20 amp circuit run through an uninsulated attic, or bundled with several others through a single bored hole, is the case where 12 AWG stops being sufficient.

THHN in Conduit

Individual 12 AWG THHN conductors in conduit are standard in commercial work, in garages and basements where conduit is exposed, and anywhere the wiring method needs to be changed later. THHN is rated 90°C dry and is dual-rated THHN/THWN-2 for wet locations, but NEC 110.14(C) still holds the circuit to its terminations, so the usable column is 60°C or 75°C and the conductor is 12 AWG either way. Conduit sizing comes from the fill tables in NEC Chapter 9.

UF-B for Direct Burial

Type UF-B is the cable for a buried 20 amp circuit to a garage, a shed or a yard receptacle, and 12/2 UF-B is the usual assembly. Burial depth comes from NEC Table 300.5(A) and depends on the wiring method and whether the circuit is GFCI protected. These are the runs where the distance section above matters most, since a buried circuit is the expensive one to upsize afterwards.

The Equipment Grounding Conductor

12 AWG copper, or 10 AWG aluminum, from NEC Table 250.122 against the 20 ampere overcurrent device — not against the conductor size and not from the ampacity table. 20 amperes is an exact row in Table 250.122, so the figure is read directly rather than rounded up to the next listed rating, which is not true at 30, 40 or 50 amperes. In copper the equipment grounding conductor is the same size as the circuit conductor, which is a coincidence of this amperage rather than a rule.

How Much Load Can a 20 Amp Circuit Carry?

A 20 amp circuit carries 20 amperes intermittently and 16 amperes continuously — 2,400 volt-amperes and 1,920 at 120 volts, or 4,800 and 3,840 at 240 volts.

Where the 16 Amperes Comes From

The code does not state a 16 ampere limit. NEC 210.19(A)(1) requires branch-circuit conductors to have an ampacity not less than the noncontinuous load plus 125 percent of the continuous load, and NEC 210.20(A) imposes the same on the overcurrent device. Working that backwards gives the familiar number: 20 divided by 1.25 is 16.

Knowing the rule rather than the number matters because most circuits carry a mixture. A circuit with 10 amperes of continuous load and 6 amperes of noncontinuous load needs 6 plus 12.5, or 18.5 amperes of conductor ampacity and device rating — which a 20 ampere circuit supplies, where the 16 ampere figure alone would have suggested it does not.

What Counts as Continuous

A continuous load is one expected to operate for three hours or more. Electric baseboard heat qualifies, as do most commercial lighting installations and an EV charger — though an EV charger needs far more than a 20 amp circuit. Kitchen receptacles generally do not: a kettle runs for three minutes. This is why a 20 amp kitchen circuit is treated as a 20 ampere circuit in practice while a 20 amp baseboard circuit is designed around 3,840 watts.

Common Mistakes on 20 Amp Circuits

14 AWG on a 20 Amp Breaker

The headline error, covered in full above. NEC 240.4(D)(3) caps 14 AWG copper at a 15 ampere device, and the usual route to the mistake is swapping a tripping 15 ampere breaker for a 20 rather than finding out why it was tripping.

Reading the 75°C or 90°C Column by Default

NEC 110.14(C)(1)(a) grants the 60°C column for circuits rated 100 amperes or less unless the equipment is listed for more. The warmer columns are where 14 AWG looks like a 20 ampere conductor, and they are not the default at this rating.

Assuming 20 Amps Means 20 Amps Continuously

It means 16. NEC 210.19(A)(1) and 210.20(A) require 125 percent of a continuous load, which is the figure that catches out baseboard heating layouts in particular.

One Kitchen Small-Appliance Circuit Instead of Two

NEC 210.11(C)(1) requires a minimum of two. This is the most common violation in kitchen remodels and the one a homeowner notices first.

Putting Other Outlets on the Laundry or Bathroom Circuit

NEC 210.11(C)(2) and 210.11(C)(3) both require their circuits to have no other outlets, with a narrow exception allowing a bathroom circuit to serve the rest of that one bathroom. Running the hallway light off the bathroom circuit is the usual version.

Ignoring Voltage Drop on a 120 Volt Run

12 AWG at 20 amperes passes 3 percent at 44 feet and 5 percent at 75. Neither is a violation, and both are worth knowing before running a circuit to a detached garage. The inverse error is treating the 3 percent figure as enforceable and upsizing conductors to satisfy a number that NEC 90.5(C) makes advisory.

Expecting the Receptacle Rating to Match the Breaker

Table 210.21(B)(3) permits a 15 ampere receptacle on a 20 ampere multi-outlet circuit, and a single receptacle on an individual circuit under 210.21(B)(1) does not. Both errors occur — fitting 20 ampere devices everywhere out of caution, and fitting a 15 ampere device on a dedicated single-receptacle circuit where it is not permitted.

Frequently Asked Questions

The questions this page's search data carries, answered in one sentence each before any qualification. Four are editorial additions, marked in place.

What size wire for a 20 amp circuit?

12 AWG copper, or 10 AWG aluminum. In the 60°C column that NEC 110.14(C)(1)(a) makes the default for a circuit rated 100 amperes or less, 12 AWG copper carries exactly 20 amperes. 12/2 NM-B cable is the normal residential wiring method for it, and it works in conduit as well.

What size wire for a 20 amp breaker?

12 AWG copper — the same answer as for a 20 amp circuit, because at this rating the breaker and the circuit are one question. The breaker rating is what the conductor must match: NEC 240.4(D)(5) permits a 20 ampere overcurrent device on 12 AWG copper, and NEC 240.4(D)(3) limits 14 AWG to 15 amperes.

Can you use 14 AWG wire on a 20 amp breaker?

No. NEC 240.4(D)(3) limits the overcurrent device on 14 AWG copper to 15 amperes, whatever the ampacity table says. 14 AWG copper does carry 20 amperes at 90°C, which is why the mistake looks reasonable — but it cannot be protected at 20 amperes, so a 20 ampere breaker on 14 AWG is a violation. Editorial addition — no keyword in this page's data asks this directly.

What size wire for a 20 amp 240 volt circuit?

12 AWG copper — the same conductor as a 120 volt 20 amp circuit, because ampacity does not depend on voltage. What changes is the breaker, which is two-pole, and the voltage drop, which halves: 12 AWG at 20 amperes holds 3 percent to 89 feet at 240 volts against 44 feet at 120 volts.

What size wire for a 20 amp outlet?

12 AWG copper, the same as for the circuit, because the conductor is sized against the breaker rather than against the receptacle. The receptacle itself may be rated 15 or 20 amperes on a multi-outlet 20 ampere circuit under NEC 210.21(B)(3) — a 15 ampere receptacle on a 20 ampere circuit is permitted and extremely common.

Can you put a 15 amp receptacle on a 20 amp circuit?

Yes, where the circuit serves two or more outlets. Table 210.21(B)(3) permits a 15 or 20 ampere receptacle on a 20 ampere branch circuit. The exception is a single receptacle on an individual branch circuit, which NEC 210.21(B)(1) requires to match the circuit rating — and a duplex receptacle counts as two receptacles, not one. Editorial addition — this question is not in the keyword data.

How far can you run 12 gauge wire on a 20 amp circuit?

About 44 feet at 120 volts before voltage drop passes 3 percent, and 89 feet at 240 volts. Those are performance targets from an informational note rather than code limits, so a longer run is not a violation — but 12 AWG at 120 volts and 20 amperes reaches 5 percent by 75 feet, and 10 AWG buys you 74 feet at 3 percent.

What size ground wire for a 20 amp circuit?

12 AWG copper, or 10 AWG aluminum, from NEC Table 250.122 against the 20 ampere overcurrent device. 20 amperes is an exact row in that table, so no rounding up is needed. The equipment grounding conductor happens to be the same size as the circuit conductor in copper, which is coincidence rather than a rule.

How many watts can a 20 amp circuit handle?

2,400 watts at 120 volts, but only 1,920 watts for a continuous load. NEC 210.19(A)(1) and 210.20(A) require the conductor and the overcurrent device to be sized for 125 percent of a continuous load, which works backwards to 16 amperes on a 20 ampere circuit. At 240 volts the figures are 4,800 and 3,840 watts. Editorial addition — this question is not in the keyword data.

How many 20 amp circuits does a kitchen need?

At least two. NEC 210.11(C)(1) requires a minimum of two 20 ampere small-appliance branch circuits for the kitchen and dining receptacles specified in 210.52(B). A single 20 ampere kitchen circuit is the most common violation found in remodels. Editorial addition — included on code grounds; no keyword in this page's data asks it.

Conductor sizes and ampacity figures on this page are taken from NEC Table 310.16 as published in NFPA 70-2023 and verified against independent reproductions; the overcurrent limits are NEC 240.4(D), the equipment grounding conductor is from NEC Table 250.122, and the voltage drop figures are computed from NEC Chapter 9 Table 9. The 3 percent voltage drop figure is from NEC 210.19(A), Informational Note No. 4, which NEC 90.5(C) makes informational rather than enforceable. These figures are provided for planning. Conductor sizing affects safety; for anything affecting code compliance, confirm with a licensed electrician and with the NEC edition your jurisdiction has adopted. The code itself is available from the NFPA.